320 Parameters
Defines the start speed (Hz/rpm) for the second auxiliary
motor. See parameter
Vector:
1300 rpm;
Scalar 48 Hz;
58 Hz
(
Defines the start speed (Hz/rpm) for the third auxiliary motor.
See parameter
Vector:
1300 rpm;
Scalar 48 Hz;
58 Hz
(
Defines the stop speed (Hz/rpm) for the first auxiliary motor.
When the speed of the motor connected directly to the drive
falls below this value and one auxiliary motor is running, the
stop delay defined by parameter
is started.
If the speed is still at the same level or lower when the stop
delay elapses, the first auxiliary motor stops.
The running speed of the drive is increased by [
-
] after the auxiliary motor stops
Vector:
800 rpm;
Scalar 25 Hz;
30 Hz
(
0…32767 rpm/Hz
Speed/frequency
1 = 1 unit
Defines the stop speed (Hz/rpm) for the second auxiliary
motor. See parameter
.
Vector:
800 rpm;
Scalar 25 Hz;
30 Hz
(
Defines the stop speed (Hz/rpm) for the third auxiliary motor.
See parameter
.
Vector:
800 rpm;
Scalar 25 Hz;
30 Hz
(
Defines a start delay for auxiliary motors. See parameter
10.00 s
0.00…12600.00 s
Time delay.
1 = 1 s
Defines a stop delay for auxiliary motors. See parameter
.
10.00 s
0.00…12600.00 s
Time delay.
1 = 1 s
Hold time for auxiliary motor switch-on. See parameter
.
0.00 s
0.00…1000.00 s
Time.
1 = 1 s
Hold time for auxiliary motor switch-off. See parameter
0.00 s
0.00…1000.00 s
Time.
1 = 1 s
Start delay for the motor that is directly controlled by the drive.
This does not affect the starting of the auxiliary motors.
WARNING!
There must always be a delay set if the
motors are equipped with star-delta starters. The
delay must be set longer than the time setting of the
starter. After the motor is switched on by the relay output of
the drive, there must be enough time for the star-delta starter
to first switch to star and then back to delta before the motor
is connected to the drive.
0.50 s
0.20…600.00 s
Time delay.
1 = 1 s
No.
Name/Value
Description
Def/FbEq16
ACS580 FW.book Page 320 Wednesday, September 21, 2016 9:48 PM
Содержание ACS580 Series
Страница 88: ...84 ACS580 FW book Page 84 Wednesday September 21 2016 9 48 PM ...
Страница 146: ...142 Program features ACS580 FW book Page 142 Wednesday September 21 2016 9 48 PM ...
Страница 444: ...440 Fieldbus control through a fieldbus adapter ACS580 FW book Page 440 Wednesday September 21 2016 9 48 PM ...
Страница 461: ...ACS580 FW book Page 457 Wednesday September 21 2016 9 48 PM ...
Страница 462: ...3AXD0000016097 Rev D EN 2016 09 02 ACS580 FW book Page 458 Wednesday September 21 2016 9 48 PM ...