Start-up, control with I/O and ID run 25
How to control the drive through the I/O interface
The table below describes how to operate the drive through the digital and analog
inputs when:
• the motor start-up is performed, and
• the default parameter settings of the ABB standard macro are in use.
Preliminary settings
If you need to change the direction of rotation, check
that limits allow reverse direction: Go to
Menu -
Primary settings - Limits
and make sure that the
minimum limit has a negative value and the maximum
limit has a positive value.
Make sure that the control connections are wired
according to the connection diagram given for the ABB
standard macro.
See section
on
Make sure that the drive is in remote control. Press
key
to switch between remote and local
control.
In remote control, the panel display
shows text
Remote
at the top left.
Starting and controlling the speed of the motor
Start by switching digital input DI1 on.
The arrow starts rotating. It is dotted until the setpoint
is reached.
Regulate the drive output frequency (motor speed) by
adjusting voltage of analog input AI1.
Changing the direction of the motor rotation
Reverse direction: Switch digital input DI2 on.
Forward direction: Switch digital input DI2 off.
Loc/Rem
ACS580 FW.book Page 25 Wednesday, September 21, 2016 9:48 PM
Содержание ACS580 Series
Страница 88: ...84 ACS580 FW book Page 84 Wednesday September 21 2016 9 48 PM ...
Страница 146: ...142 Program features ACS580 FW book Page 142 Wednesday September 21 2016 9 48 PM ...
Страница 444: ...440 Fieldbus control through a fieldbus adapter ACS580 FW book Page 440 Wednesday September 21 2016 9 48 PM ...
Страница 461: ...ACS580 FW book Page 457 Wednesday September 21 2016 9 48 PM ...
Страница 462: ...3AXD0000016097 Rev D EN 2016 09 02 ACS580 FW book Page 458 Wednesday September 21 2016 9 48 PM ...