Fault tracing 393
5691
Measurement circuit
ADC
Measurement circuit fault.
Contact your local ABB representative.
5692
PU board powerfail
Power unit power supply
failure.
Contact your local ABB representative.
5693
Measurement circuit
DFF
Measurement circuit fault.
Contact your local ABB representative.
5696
PU state feedback
State feedback from output
phases does not match control
signals.
Contact your local ABB representative.
5697
Charging feedback
Charging feedback signal
missing.
Check the feedback signal coming from
the charging system
6181
FPGA version
incompatible
Firmware and FPGA versions
are incompatible.
Reboot the control unit (using parameter
) or by cycling
power. If the problem persists, contact
your local ABB representative
6306
FBA A mapping file
Fieldbus adapter A mapping
file read error.
Contact your local ABB representative.
6481
Task overload
Internal fault.
Reboot the control unit (using parameter
) or by cycling
power. If the problem persists, contact
your local ABB representative
6487
Stack overflow
Internal fault.
Reboot the control unit (using parameter
) or by cycling
power. If the problem persists, contact
your local ABB representative
64A1
Internal file load
File read error.
Reboot the control unit (using parameter
) or by cycling
power. If the problem persists, contact
your local ABB representative
64B2
User set fault
Loading of user parameter set
failed because
• requested set does not exist
• set is not compatible with
control program
• drive was switched off
during loading.
Ensure that a valid user parameter set
exists. Reload if uncertain.
64E1
Kernel overload
Operating system error.
Reboot the control unit (using parameter
) or by cycling
power. If the problem persists, contact
your local ABB representative
6581
Parameter system
Parameter load or save failed.
Try forcing a save using parameter
. Retry.
65A1
FBA A parameter
conflict
The drive does not have a
functionality requested by
PLC, or requested functionality
has not been activated.
Check PLC programming.
Check settings of parameter groups
and
.
6681
EFB comm loss
Programmable fault:
Communication break in
embedded fieldbus (EFB)
communication.
Check the status of the fieldbus master
(online/offline/error etc.).
Check cable connections to the
EIA-485/X5 terminals 29, 30 and 31 on
the control unit.
Code
(hex)
Fault / Aux. code
Cause
What to do
ACS580 FW.book Page 393 Wednesday, September 21, 2016 9:48 PM
Содержание ACS580 Series
Страница 88: ...84 ACS580 FW book Page 84 Wednesday September 21 2016 9 48 PM ...
Страница 146: ...142 Program features ACS580 FW book Page 142 Wednesday September 21 2016 9 48 PM ...
Страница 444: ...440 Fieldbus control through a fieldbus adapter ACS580 FW book Page 440 Wednesday September 21 2016 9 48 PM ...
Страница 461: ...ACS580 FW book Page 457 Wednesday September 21 2016 9 48 PM ...
Страница 462: ...3AXD0000016097 Rev D EN 2016 09 02 ACS580 FW book Page 458 Wednesday September 21 2016 9 48 PM ...