Parameters 331
Timed function 1
Bit 0 of
(see page
).
18
Timed function 2
Bit 1 of
(see page
).
19
Timed function 3
Bit 2 of
(see page
).
20
Reserved
21…23
Supervision 1
Bit 0 of
(see page
).
24
Supervision 2
Bit 1 of
(see page
).
25
Supervision 3
Bit 2 of
(see page
).
26
Source selection (see
). -
.
Selects the unit of parameters indicating power, temperature
and torque.
0000b
0000h…FFFFh
Unit selection word.
1 = 1
Clears all events from the drive’s fault and event logs.
Done
1 = No action
0
Clear
1 = Clear the loggers.
1
0…1
1 = 1
(Visible when user lock is open)
To change the current user pass code, enter a new code into
this parameter as well as
warning will be active until the new pass code is confirmed.
To cancel changing the pass code, close the user lock without
confirming. To close the lock, enter an invalid pass code in
parameter
, activate parameter
, or cycle the power.
See also section
10000000
10000000…
99999999
New user pass code.
-
(Visible when user lock is open)
Confirms the new user pass code entered in
.
10000000…
99999999
Confirmation of new user pass code.
-
No.
Name/Value
Description
Def/FbEq16
Bit
Name
Information
0
Power unit
0 = kW
1 = hp
1
Reserved
2
Temperature
unit
0 = °C
1 = °F
3
Reserved
4
Torque unit
0 = Nm (N·m)
1 = lbft (lb·ft)
5…15
Reserved
ACS580 FW.book Page 331 Wednesday, September 21, 2016 9:48 PM
Содержание ACS580 Series
Страница 88: ...84 ACS580 FW book Page 84 Wednesday September 21 2016 9 48 PM ...
Страница 146: ...142 Program features ACS580 FW book Page 142 Wednesday September 21 2016 9 48 PM ...
Страница 444: ...440 Fieldbus control through a fieldbus adapter ACS580 FW book Page 440 Wednesday September 21 2016 9 48 PM ...
Страница 461: ...ACS580 FW book Page 457 Wednesday September 21 2016 9 48 PM ...
Страница 462: ...3AXD0000016097 Rev D EN 2016 09 02 ACS580 FW book Page 458 Wednesday September 21 2016 9 48 PM ...