120 Program features
See also the block diagram on page
Notes:
• Jogging is not available when the drive is in local control.
• Jogging cannot be enabled when the drive start command is on, or the drive
started when jogging is d. Starting the drive after the jog switches off requires a
fresh start command.
WARNING!
If jogging is enabled and activated while the start command is on,
jogging will activate as soon as the start command switches off.
• If both jogging functions are activated, the one that was activated first has priority.
• Jogging uses vector control.
• The inching functions activated through fieldbus (see
,
bits 8…9) use the references and ramp times defined for jogging, but do not
require the jog signal.
8-9
0
1->0
0
Drive is stopped. As long as the jog signal is on, start
commands are ignored. After jog switches off, a fresh start
command is required.
9-10
x
0
1
Drive accelerates to the speed reference along the selected
acceleration ramp (parameters
10-11
x
0
1
Drive follows the speed reference.
11-12
x
0
0
Drive decelerates to zero speed along the selected
deceleration ramp (parameters
…
).
12-13
x
0
0
Drive is stopped.
13-14
x
0
1
Drive accelerates to the speed reference along the selected
acceleration ramp (parameters
14-15
x
0->1
1
Drive follows the speed reference. As long as the start
command is on, the jog signal is ignored. If the jog signal is
on when the start command switches off, jogging is enabled
immediately.
15-16
0->1
1
0
Start command switches off. The drive starts to decelerate
along the selected deceleration ramp (parameters
…
When the jog command switches on, the decelerating drive
adopts the deceleration ramp of the jogging function.
16-17
1
1
0
Drive follows the jog reference.
17-18
0
1->0
0
Drive decelerates to zero speed along the deceleration ramp
of the jogging function.
Phase
Jog
cmd
Jog
Start
cmd
Description
ACS580 FW.book Page 120 Wednesday, September 21, 2016 9:48 PM
Содержание ACS580 Series
Страница 88: ...84 ACS580 FW book Page 84 Wednesday September 21 2016 9 48 PM ...
Страница 146: ...142 Program features ACS580 FW book Page 142 Wednesday September 21 2016 9 48 PM ...
Страница 444: ...440 Fieldbus control through a fieldbus adapter ACS580 FW book Page 440 Wednesday September 21 2016 9 48 PM ...
Страница 461: ...ACS580 FW book Page 457 Wednesday September 21 2016 9 48 PM ...
Страница 462: ...3AXD0000016097 Rev D EN 2016 09 02 ACS580 FW book Page 458 Wednesday September 21 2016 9 48 PM ...