288 Parameters
Timed function 3
(see page
).
20
Supervision 1
(see page
).
21
Supervision 2
(see page
).
22
Supervision 3
(see page
).
23
Source selection (see
on page
). -
Prevention of PID integration term increase for PID set 1.
No
Increase prevention not in use.
0
Limiting
The PID integration term is not increased if the maximum
value for the PID output is reached. This parameter is valid
for the PID set 1.
1
Ext PID min lim
The process PID integration term is not increased when the
output of the external PID has reached its minimum limit. In
this setup, the external PID is used as a source for the
process PID. This parameter is valid for the PID set 1.
2
Ext PID max lim
The process PID integration term is not increased when the
output of the external PID has reached its maximum limit. In
this setup, the external PID is used as a source for the
process PID. This parameter is valid for the PID set 1.
3
Source selection (see
on page
). -
Prevention of PID integration term decrease for PID set 1.
No
Decrease prevention not in use.
0
Limiting
The PID integration term is not decreased if the minimum
value for the PID output is reached. This parameter is valid
for the PID set 1.
1
Ext PID min lim
The process PID integration term is not decreased when the
output of the external PID has reached its minimum limit. In
this setup, the external PID is used as a source for the
process PID. This parameter is valid for the PID set 1.
2
Ext PID max lim
The process PID integration term is not decreased when the
output of the external PID has reached its maximum limit. In
this setup, the external PID is used as a source for the
process PID. This parameter is valid for the PID set 1.
3
Source selection (see
on page
). -
Displays the value of the internal setpoint. See the control
chain diagram on page
This parameter is read-only.
-
-32768.00…
32767.00 PID
customer units
Process PID internal setpoint.
1 = 1 PID
customer unit
Storage parameter for receiving a process feedback value eg.
through the embedded fieldbus interface.
The value can be sent to the drive as Modbus I/O data. Set
the target selection parameter of that particular data
(
…
) to
. In
(or
), select
.
-
-327.68…327.67
Storage parameter for process feedback.
100 = 1
No.
Name/Value
Description
Def/FbEq16
ACS580 FW.book Page 288 Wednesday, September 21, 2016 9:48 PM
Содержание ACS580 Series
Страница 88: ...84 ACS580 FW book Page 84 Wednesday September 21 2016 9 48 PM ...
Страница 146: ...142 Program features ACS580 FW book Page 142 Wednesday September 21 2016 9 48 PM ...
Страница 444: ...440 Fieldbus control through a fieldbus adapter ACS580 FW book Page 440 Wednesday September 21 2016 9 48 PM ...
Страница 461: ...ACS580 FW book Page 457 Wednesday September 21 2016 9 48 PM ...
Страница 462: ...3AXD0000016097 Rev D EN 2016 09 02 ACS580 FW book Page 458 Wednesday September 21 2016 9 48 PM ...