148 Parameters
Drive output power. The unit is selected by parameter
. A filter time constant for this signal can be
-
-32768.00…
32767.00 kW or hp
Output power.
1 = 1 unit
Output power in percent of the nominal motor power.
-
-300.00… 300.00% Output power.
1 = 1%
Output power in percent of the nominal drive power.
-
-300.00… 300.00% Output power.
1 = 1%
Estimated mechanical power at motor shaft.
-
-32768.00…
32767.00 kW or hp
Motor shaft power.
1 = 1 unit
Amount of energy that has passed through the drive (in either
direction) in full gigawatt-hours. The minimum value is zero.
-
0…65535 GWh
Energy in GWh.
1 = 1 GWh
Amount of energy that has passed through the drive (in either
direction) in full megawatt-hours. Whenever the counter rolls
over,
is incremented. The
minimum value is zero.
-
0…1000 MWh
Energy in MWh.
1 = 1 MWh
Amount of energy that has passed through the drive (in either
direction) in full kilowatt-hours. Whenever the counter rolls
over,
is incremented. The
minimum value is zero.
-
0…1000 kWh
Energy in kWh.
10 = 1 kWh
Used flux reference in percent of nominal flux of motor.
-
0…200%
Flux reference.
1 = 1%
Torque that corresponds to 100% of nominal motor torque.
The unit is selected by parameter
.
Note:
This value is copied from parameter
if entered. Otherwise the value is calculated
from other motor data.
-
0.000…4000000
N·m or lb·ft
Nominal torque.
1 = 100 unit
Current hour energy consumption. This is the energy of the
last 60 minutes (not necessarily continuous) the drive has
been running, not the energy of a calendar hour. The value is
set to the value before the power cycle when the drive is
again up and running.
-
0.00… 1000000.00
kWh
Energy.
1 = 1 kWh
Previous hour energy consumption. The value
is stored here when its values has been cumulated
for 60 minutes. The value is set to the value before the power
cycle when the drive is again up and running.
-
0.00… 1000000.00
kWh
Energy.
1 = 1 kWh
No.
Name/Value
Description
Def/FbEq16
ACS580 FW.book Page 148 Wednesday, September 21, 2016 9:48 PM
Содержание ACS580 Series
Страница 88: ...84 ACS580 FW book Page 84 Wednesday September 21 2016 9 48 PM ...
Страница 146: ...142 Program features ACS580 FW book Page 142 Wednesday September 21 2016 9 48 PM ...
Страница 444: ...440 Fieldbus control through a fieldbus adapter ACS580 FW book Page 440 Wednesday September 21 2016 9 48 PM ...
Страница 461: ...ACS580 FW book Page 457 Wednesday September 21 2016 9 48 PM ...
Страница 462: ...3AXD0000016097 Rev D EN 2016 09 02 ACS580 FW book Page 458 Wednesday September 21 2016 9 48 PM ...