38 Program features
Cleaning sequence steps
1. The pump system meets the triggering conditions as per the operating mode
) selected. At this condition, normal operation stops and the drive uses the
target time defined in parameter
2. Acceleration for cleaning is defined by parameter
.
3. The pump runs at cleaning speed for the time defined by parameter
4. The pump decelerates to zero-speed. Time to zero speed is defined by parameter
.
5. The pump is stopped until parameter
is elapsed.
6. The pump accelerates the pump speed to positive direction. See parameter
.
7. The pump runs at the positive cleaning speed. See parameter
.
8. The pump decreases the pump speed back to zero defined by parameter
9. The drive waits until the parameter
cleaning sequence starts or normal operation starts.
10. The pump starts following speed/frequency reference of the active control
location. During acceleration to speed/frequency, the drive follows pump cleaning
acceleration time
.
The cleaning sequence starts based on the selected triggering conditions. The
cleaning sequence follows the diagram on page
.
You can start the pump cleaning sequence in these conditions:
• On start cleaning now (defined by parameter
• Manually (for example, DI4 to DI6, defined by parameter
Settings
Parameter group
(page
Dry run protection
The dry run protection function automatically detects and avoids running of a pump
with no flow of water in the pump. The condition at which the pump runs with no load
is called as dry run condition. The dry run protection can be activated through any of
the following method:
• Dry run protection through DI
• Dry run protection through minimum load current
ACQ80 FW.book Page 38 Thursday, February 14, 2019 11:33 AM
Содержание ACQ80-04 Series
Страница 4: ...4 ACQ80 FW book Page 4 Thursday February 14 2019 11 33 AM ...
Страница 10: ...10 Table of contents ACQ80 FW book Page 10 Thursday February 14 2019 11 33 AM ...
Страница 16: ...16 Introduction to the manual ACQ80 FW book Page 16 Thursday February 14 2019 11 33 AM ...
Страница 26: ...26 Start up control with I O and ID run ACQ80 FW book Page 26 Thursday February 14 2019 11 33 AM ...
Страница 28: ...28 Using the control panel ACQ80 FW book Page 28 Thursday February 14 2019 11 33 AM ...
Страница 54: ...54 Program features ACQ80 FW book Page 54 Thursday February 14 2019 11 33 AM ...
Страница 196: ...196 Additional parameter data ACQ80 FW book Page 196 Thursday February 14 2019 11 33 AM ...
Страница 220: ...220 Fault tracing ACQ80 FW book Page 220 Thursday February 14 2019 11 33 AM ...
Страница 260: ...260 Fieldbus control through a fieldbus adapter ACQ80 FW book Page 260 Thursday February 14 2019 11 33 AM ...
Страница 264: ...264 Parameterization with drive composer ACQ80 FW book Page 264 Thursday February 14 2019 11 33 AM ...
Страница 268: ...268 Parameterization with automation builder drive manager ACQ80 FW book Page 268 Thursday February 14 2019 11 33 AM ...