Start-up, control with I/O and ID run 25
ID run procedure
Pre-check
WARNING!
The motor will run at up to approximately 50…80% of the nominal
speed during the ID run. The motor will rotate in the forward direction.
Make
sure that it is safe to run the motor before performing the ID run!
De-couple the motor from the driven equipment
Check that the values of the motor data parameters are equivalent to those on the motor
nameplate.
Check that the STO circuit is closed.
If parameter values (from group
to group
) are changed
before the ID run, check that the new settings meet the following conditions:
Parameter
< 0 rpm
Parameter
= motor rated speed (Normal ID run procedure needs
the motor to be run at 100% speed.)
Parameter
> 50%
Make sure that the panel is in local control (text
Local
shown at the top left).
Press key
to switch between local and remote control modes.
ID run
Navigate to
Main menu
→
Complete
parameter list
→
parameter
and
select the required ID run type.
Press
(
OK
)
Panel LED starts blinking green to indicate an
active warning (
).
You can hide the warning view by pressing
(
Back
).
Press the start key
(
)
to start the ID run.
Note:
In general, it is recommended not to press
any control panel keys during the ID run.
However, you can stop the ID run at any time by
pressing the stop key
(
)
.
During the ID run the arrow rotates at the top.
After the ID run is completed, the arrow stops
rotating and the rpm turns to 0.00.
If the ID run fails, fault
is shown. For
more information, see chapter
page
.
Note:
You must repeat the ID run procedure if
you have changed the motor parameters (
) after the ID run was competed.
Loc/Rem
Max
99.13
[0]
[1]
[2]
Warning: AFF6
Max
99.13
[0]
[1]
[2]
Rem
1304rpm
1304
rpm
Rem
0.0rpm
0.00
rpm
ACQ80 FW.book Page 25 Thursday, February 14, 2019 11:33 AM
Содержание ACQ80-04 Series
Страница 4: ...4 ACQ80 FW book Page 4 Thursday February 14 2019 11 33 AM ...
Страница 10: ...10 Table of contents ACQ80 FW book Page 10 Thursday February 14 2019 11 33 AM ...
Страница 16: ...16 Introduction to the manual ACQ80 FW book Page 16 Thursday February 14 2019 11 33 AM ...
Страница 26: ...26 Start up control with I O and ID run ACQ80 FW book Page 26 Thursday February 14 2019 11 33 AM ...
Страница 28: ...28 Using the control panel ACQ80 FW book Page 28 Thursday February 14 2019 11 33 AM ...
Страница 54: ...54 Program features ACQ80 FW book Page 54 Thursday February 14 2019 11 33 AM ...
Страница 196: ...196 Additional parameter data ACQ80 FW book Page 196 Thursday February 14 2019 11 33 AM ...
Страница 220: ...220 Fault tracing ACQ80 FW book Page 220 Thursday February 14 2019 11 33 AM ...
Страница 260: ...260 Fieldbus control through a fieldbus adapter ACQ80 FW book Page 260 Thursday February 14 2019 11 33 AM ...
Страница 264: ...264 Parameterization with drive composer ACQ80 FW book Page 264 Thursday February 14 2019 11 33 AM ...
Страница 268: ...268 Parameterization with automation builder drive manager ACQ80 FW book Page 268 Thursday February 14 2019 11 33 AM ...