Parameters 79
Allows the data value of a forced digital input to be changed
from 0 to 1. It is only possible to force an input that has been
selected in parameter
.
Bit 0 is the forced value for DI1; bit 5 is the forced value for
the DI6.
0b0000
0b0000...0b1111
Forced values of digital inputs.
1 = 1
Status of relay outputs RO1…RO3.
0b0000
0b0000...0b1111
Status of relay outputs.
1 = 1
The signals connected to the relay outputs can be overridden
for eg. testing purposes. A bit in parameter
is provided for each relay output, and its value is applied
whenever the corresponding bit in this parameter is 1.
Note:
Boot and power cycle reset the force selections
(parameters
).
0b0000
0b0000...0b1111
Override selection for relay outputs.
1 = 1
Contains the values of relay outputs that are used instead of
the connected signals if selected in parameter
. Bit 0 is the forced value for RO1.
0b0000
0b0000...0b1111
Forced RO values.
1 = 1
No.
Name/Value
Description
Def/FbEq16
Bit
Value
0
Force the value of this bit to D1, if so defined in parameter
1
Force the value of this bit to D3, if so defined in parameter
2
Force the value of this bit to D3, if so defined in parameter
3
Force the value of this bit to D4, if so defined in parameter
4
Force the value of this bit to D5, if so defined in parameter
5
Force the value of this bit to D6, if so defined in parameter
6…15
Reserved
Bit
Value
0
1 = RO1 is energized.
1
1 = RO2 is energized.
2
1 = RO3 is energized.
3…15
Reserved
Bit
Value
0
1 = Force RO1 to value of bit 0 of parameter
. (0 = Normal mode)
1
1 = Force RO2 to value of bit 1 of parameter
. (0 = Normal mode)
2
1 = Force RO3 to value of bit 2 of parameter
. (0 = Normal mode)
3…15
Reserved
Bit
Value
0
Force the value of this bit to RO1, if so defined in parameter
1
Force the value of this bit to RO2, if so defined in parameter
2
Force the value of this bit to RO3, if so defined in parameter
3…15
Reserved
ACQ80 FW.book Page 79 Thursday, February 14, 2019 11:33 AM
Содержание ACQ80-04 Series
Страница 4: ...4 ACQ80 FW book Page 4 Thursday February 14 2019 11 33 AM ...
Страница 10: ...10 Table of contents ACQ80 FW book Page 10 Thursday February 14 2019 11 33 AM ...
Страница 16: ...16 Introduction to the manual ACQ80 FW book Page 16 Thursday February 14 2019 11 33 AM ...
Страница 26: ...26 Start up control with I O and ID run ACQ80 FW book Page 26 Thursday February 14 2019 11 33 AM ...
Страница 28: ...28 Using the control panel ACQ80 FW book Page 28 Thursday February 14 2019 11 33 AM ...
Страница 54: ...54 Program features ACQ80 FW book Page 54 Thursday February 14 2019 11 33 AM ...
Страница 196: ...196 Additional parameter data ACQ80 FW book Page 196 Thursday February 14 2019 11 33 AM ...
Страница 220: ...220 Fault tracing ACQ80 FW book Page 220 Thursday February 14 2019 11 33 AM ...
Страница 260: ...260 Fieldbus control through a fieldbus adapter ACQ80 FW book Page 260 Thursday February 14 2019 11 33 AM ...
Страница 264: ...264 Parameterization with drive composer ACQ80 FW book Page 264 Thursday February 14 2019 11 33 AM ...
Страница 268: ...268 Parameterization with automation builder drive manager ACQ80 FW book Page 268 Thursday February 14 2019 11 33 AM ...