204 Fault tracing
1 Slip frequency is too small.
Check the settings of the motor
configuration parameters in groups 98
and 99.
Check that the drive is sized correctly for
the motor.
2 Synchronous and nominal
speeds differ too much.
3 Nominal speed is higher than
synchronous speed with 1 pole
pair.
4 Nominal current is outside
limits
5 Nominal voltage is outside
limits.
6 Nominal power is higher than
apparent power.
7 Nominal power not consistent
with nominal speed and
torque.
A6A5
No motor data
Parameters in group 99 have
not been set.
Check that all the required parameters in
group 99 have been set.
Note:
It is normal for this warning to
appear during the start-up and continue
until the motor data is entered.
A6A6
Voltage category
unselected
The voltage category has not
been defined.
Set voltage category in parameter
.
A6A7
System time not set
System time is not set.
A6B0
User lock is open
The user lock is open, ie. user
lock configuration parameters
…
are visible.
Close the user lock by entering an invalid
pass code in parameter
(page
).
A6B1
User pass code not
confirmed
A new user pass code has
been entered in parameter
but not confirmed in
.
Confirm the new pass code by entering
the same code in
. To cancel,
close the user lock without confirming the
new code. See section
(page
A6D1
FBA A parameter
conflict
The drive does not have a
functionality requested by a
PLC, or requested functionality
has not been activated.
Check PLC programming.
Check settings of parameter groups
A6E5
AI parametrization
The current/voltage hardware
setting of an analog input does
not correspond to parameter
settings.
Check the event log for an auxiliary code.
The code identifies the analog input
whose settings are in conflict.
Adjust either the hardware setting (on the
drive control unit) or parameter
Note:
Control board reboot (either by
cycling the power or through parameter
) is required to
validate any changes in the hardware
settings.
A780
Motor stall
(Programmable
warning:
)
Motor is operating in stall
region.
Check motor load, drive ratings and fault
function parameters.
Code
(hex)
Warning / Aux. code
(
aux code visible only
on assistant control
panel and drive
composer
)
Cause
What to do
ACQ80 FW.book Page 204 Thursday, February 14, 2019 11:33 AM
Содержание ACQ80-04 Series
Страница 4: ...4 ACQ80 FW book Page 4 Thursday February 14 2019 11 33 AM ...
Страница 10: ...10 Table of contents ACQ80 FW book Page 10 Thursday February 14 2019 11 33 AM ...
Страница 16: ...16 Introduction to the manual ACQ80 FW book Page 16 Thursday February 14 2019 11 33 AM ...
Страница 26: ...26 Start up control with I O and ID run ACQ80 FW book Page 26 Thursday February 14 2019 11 33 AM ...
Страница 28: ...28 Using the control panel ACQ80 FW book Page 28 Thursday February 14 2019 11 33 AM ...
Страница 54: ...54 Program features ACQ80 FW book Page 54 Thursday February 14 2019 11 33 AM ...
Страница 196: ...196 Additional parameter data ACQ80 FW book Page 196 Thursday February 14 2019 11 33 AM ...
Страница 220: ...220 Fault tracing ACQ80 FW book Page 220 Thursday February 14 2019 11 33 AM ...
Страница 260: ...260 Fieldbus control through a fieldbus adapter ACQ80 FW book Page 260 Thursday February 14 2019 11 33 AM ...
Страница 264: ...264 Parameterization with drive composer ACQ80 FW book Page 264 Thursday February 14 2019 11 33 AM ...
Страница 268: ...268 Parameterization with automation builder drive manager ACQ80 FW book Page 268 Thursday February 14 2019 11 33 AM ...