![ABB ACQ80-04 Series Скачать руководство пользователя страница 215](http://html.mh-extra.com/html/abb/acq80-04-series/acq80-04-series_firmware-manual_2932215.webp)
Fault tracing 215
6684
EFB load fault
Embedded fieldbus (EFB)
protocol firmware could not be
loaded.
Contact your local ABB representative.
Version mismatch between
EFB protocol firmware and
drive firmware.
6685
EFB fault 2
Fault reserved for the EFB
protocol application.
Check the documentation of the protocol.
6686
EFB fault 3
Fault reserved for the EFB
protocol application.
Check the documentation of the protocol.
6882
Text 32-bit table
overflow
Internal fault.
Reset the fault. Contact your local ABB
representative if the fault persists.
6885
Text file overflow
Internal fault.
Reset the fault. Contact your local ABB
representative if the fault persists.
7081
Control panel loss
Programmable fault:
Control panel or PC tool
selected as active control
location for drive has ceased
communicating.
Check PC tool or control panel
connection.
Check control panel connector.
Disconnect and reconnect the control
panel.
7082
I/O module comm loss Communication between IO
module and drive is not
working properly.
Check installation of IO module.
7085
Incompatible option
module
Fieldbus option module not
supported.
Replace the module with a supported
type.
7086
I/O module AI
overvoltage
Overvoltage detected in AI. AI
is changed to voltage mode
from mA mode. AI will return
automatically back to mA
mode when the AI signal level
is within acceptable limits.
Check AI signal levels.
7100
Excitation current
Excitation current feedback
low or missing
Contact your local ABB representative.
7121
Motor stall
Programmable fault:
Motor is operating in stall
region because of e.g.
excessive load or insufficient
motor power.
Check motor load and drive ratings.
Check fault function parameters.
7122
Motor overload
Motor current is too high.
Check for overloaded motor
Adjust the parameters used for the motor
overload function. (
…
,
,
)
7181
Brake resistor
Brake resistor broken or not
connected.
Check that a brake resistor has been
connected.
Check the condition of the brake resistor.
Check the dimensioning of the brake
resistor.
Code
(hex)
Fault / Aux. code
(
aux
code visible only on
assistant control panel
and drive composer
)
Cause
What to do
ACQ80 FW.book Page 215 Thursday, February 14, 2019 11:33 AM
Содержание ACQ80-04 Series
Страница 4: ...4 ACQ80 FW book Page 4 Thursday February 14 2019 11 33 AM ...
Страница 10: ...10 Table of contents ACQ80 FW book Page 10 Thursday February 14 2019 11 33 AM ...
Страница 16: ...16 Introduction to the manual ACQ80 FW book Page 16 Thursday February 14 2019 11 33 AM ...
Страница 26: ...26 Start up control with I O and ID run ACQ80 FW book Page 26 Thursday February 14 2019 11 33 AM ...
Страница 28: ...28 Using the control panel ACQ80 FW book Page 28 Thursday February 14 2019 11 33 AM ...
Страница 54: ...54 Program features ACQ80 FW book Page 54 Thursday February 14 2019 11 33 AM ...
Страница 196: ...196 Additional parameter data ACQ80 FW book Page 196 Thursday February 14 2019 11 33 AM ...
Страница 220: ...220 Fault tracing ACQ80 FW book Page 220 Thursday February 14 2019 11 33 AM ...
Страница 260: ...260 Fieldbus control through a fieldbus adapter ACQ80 FW book Page 260 Thursday February 14 2019 11 33 AM ...
Страница 264: ...264 Parameterization with drive composer ACQ80 FW book Page 264 Thursday February 14 2019 11 33 AM ...
Страница 268: ...268 Parameterization with automation builder drive manager ACQ80 FW book Page 268 Thursday February 14 2019 11 33 AM ...