160 Parameters
Defines the nominal speed of pump. This value is used
for flow calculation (
).
0
0...30000 rpm
Speed.
1 = 1
Defines the minimum speed/frequency limit below which flow
is not calculated.
5.00
0.00...32767.00
Hz
Minimum speed/frequency limit for flow calculation.
1 = 1
Resets the measured flow data of actual signals to
zero in the parameters
and
.
Not selected
Disables the flow reset.
0
Reset
Activates the flow reset.
1
Defines the power input of pump at point 1 on the PQ
performance curve.
See section
0.00
0.00...32767.00 kW Power input of pump at point 1.
Defines the power input of pump at point 2 on the PQ
performance curve.
See parameter
.
0.00
Defines the power input of pump at point 3 on the PQ
performance curve.
See parameter
.
0.00
Defines the power input of pump at point 4 on the PQ
performance curve.
See parameter
.
0.00
Defines the power input of pump at point 5 on the PQ
performance curve.
See parameter
.
0.00
Defines the flow rate at point 1 on the PQ performance curve.
See section
0.00
0.00...
200000.00 m
3
/h
Flow rate at point 1 of the PQ curve.
1 = 1
Defines the flow rate at point 2 on the PQ performance curve.
See parameter
0.00
Defines the flow rate at point 3 on the PQ performance curve.
See parameter
0.00
Defines the flow rate at point 4 on the PQ performance curve.
See parameter
0.00
Defines the flow rate at point 5 on the PQ performance curve.
See parameter
0.00
82
Settings for pup dry run protection.
See section
Selects the source for dry run protection.
Not selected
0 (always off).
0
Selected
1 (always on).
1
DI1
Digital input DI1 (
, bit 0).
2
No.
Name/Value
Description
Def/FbEq16
ACQ80 FW.book Page 160 Thursday, February 14, 2019 11:33 AM
Содержание ACQ80-04 Series
Страница 4: ...4 ACQ80 FW book Page 4 Thursday February 14 2019 11 33 AM ...
Страница 10: ...10 Table of contents ACQ80 FW book Page 10 Thursday February 14 2019 11 33 AM ...
Страница 16: ...16 Introduction to the manual ACQ80 FW book Page 16 Thursday February 14 2019 11 33 AM ...
Страница 26: ...26 Start up control with I O and ID run ACQ80 FW book Page 26 Thursday February 14 2019 11 33 AM ...
Страница 28: ...28 Using the control panel ACQ80 FW book Page 28 Thursday February 14 2019 11 33 AM ...
Страница 54: ...54 Program features ACQ80 FW book Page 54 Thursday February 14 2019 11 33 AM ...
Страница 196: ...196 Additional parameter data ACQ80 FW book Page 196 Thursday February 14 2019 11 33 AM ...
Страница 220: ...220 Fault tracing ACQ80 FW book Page 220 Thursday February 14 2019 11 33 AM ...
Страница 260: ...260 Fieldbus control through a fieldbus adapter ACQ80 FW book Page 260 Thursday February 14 2019 11 33 AM ...
Страница 264: ...264 Parameterization with drive composer ACQ80 FW book Page 264 Thursday February 14 2019 11 33 AM ...
Страница 268: ...268 Parameterization with automation builder drive manager ACQ80 FW book Page 268 Thursday February 14 2019 11 33 AM ...