152 Parameters
Defines a minimum response delay in addition to any fixed
delay imposed by the protocol.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
0 ms
0…65535 ms
Minimum response delay.
1 = 1
Shows raw (unmodified) status word sent by the drive to the
Modbus controller. For debugging purposes.
This parameter is read-only.
-
0000h…FFFFh
Control word sent by Modbus controller to the drive.
1 = 1
Shows raw (unmodified) status word for debugging purposes.
This parameter is read-only.
-
0000h…FFFFh
Status word sent by the drive to the Modbus controller.
1 = 1
Defines the communication profile used by the protocol.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
ABB Drives
ABB Drives control profile (with a 16-bit control word)
0
DCU Profile
DCU control profile (with a 16 or 32-bit control word)
5
Selects the type and scaling of reference 1 received through
the embedded fieldbus interface.
The scaled reference is displayed by
.
Note:
Applicable only when
disabled. If parameter MPPT reference is enabled, then the
parameter should be set to it’s default value.
Speed or frequency Type and scaling is chosen automatically according to the
currently active operation mode as follows.
0
Transparent
No scaling is applied.
1
General
Generic reference without a specific unit. Scaling: 1 = 100.
2
Torque
Torque reference. The scaling is defined by parameter
.
3
Speed
Speed reference. The scaling is defined by parameter
.
4
Frequency
Frequency reference. The scaling is defined by parameter
5
Not applicable.
Selects the type of actual value 1.
Note:
Applicable only when
disabled. If parameter MPPT reference is enabled, then the
parameter should be set to it’s default value.
No.
Name/Value
Description
Def/FbEq16
Operation mode
Reference 1 type
Speed control
Frequency control
ACQ80 FW.book Page 152 Thursday, February 14, 2019 11:33 AM
Содержание ACQ80-04 Series
Страница 4: ...4 ACQ80 FW book Page 4 Thursday February 14 2019 11 33 AM ...
Страница 10: ...10 Table of contents ACQ80 FW book Page 10 Thursday February 14 2019 11 33 AM ...
Страница 16: ...16 Introduction to the manual ACQ80 FW book Page 16 Thursday February 14 2019 11 33 AM ...
Страница 26: ...26 Start up control with I O and ID run ACQ80 FW book Page 26 Thursday February 14 2019 11 33 AM ...
Страница 28: ...28 Using the control panel ACQ80 FW book Page 28 Thursday February 14 2019 11 33 AM ...
Страница 54: ...54 Program features ACQ80 FW book Page 54 Thursday February 14 2019 11 33 AM ...
Страница 196: ...196 Additional parameter data ACQ80 FW book Page 196 Thursday February 14 2019 11 33 AM ...
Страница 220: ...220 Fault tracing ACQ80 FW book Page 220 Thursday February 14 2019 11 33 AM ...
Страница 260: ...260 Fieldbus control through a fieldbus adapter ACQ80 FW book Page 260 Thursday February 14 2019 11 33 AM ...
Страница 264: ...264 Parameterization with drive composer ACQ80 FW book Page 264 Thursday February 14 2019 11 33 AM ...
Страница 268: ...268 Parameterization with automation builder drive manager ACQ80 FW book Page 268 Thursday February 14 2019 11 33 AM ...