Parameters 85
Shows value of analog input AI1 after scaling. See
parameters
.
This parameter is read-only.
50.000
-32768.000…
32767.000
Scaled value of analog input AI1.
1 = 1
Forced value that can be used instead of the true reading of
the input. See parameter
.
0
0.000…11.000 V
Forced value of analog input AI1.
1000 = 1 unit
Selects the unit for readings and settings related to analog
input AI1.
Note:
In firmware ASCL2 and ASCL4), this setting must
match the corresponding hardware setting on the drive
control unit. See chapter
Electrical installation
, section
Switches
in the
Hardware manual
of the drive and the default
control connections for the macro in use in chapter
(page
). Control board reboot (either by cycling the
power or through parameter
) is
required to validate any changes in the hardware settings.
V
Volts.
2
mA
Milliamperes.
10
Defines the filter time constant for analog input AI1.
Note:
The signal is also filtered due to the signal interface
hardware (approximately 0.25 ms time constant). This cannot
be changed by any parameter.
0.100 s
0.000…30.000 s
Filter time constant.
1000 = 1
Defines the minimum site value for analog input AI1.
Set the value actually sent to the drive when the analog signal
from plant is wound to its minimum setting.
See also parameter
.
0.000
0.000…11.000 V
Minimum value of AI1.
1000 = 1
No.
Name/Value
Description
Def/FbEq16
63
%
100
T
t
O = I × (1 - e
-t
/T
)
I = filter input (step)
O = filter output
t
= time
T = filter time constant
Unfiltered signal
Filtered signal
ACQ80 FW.book Page 85 Thursday, February 14, 2019 11:33 AM
Содержание ACQ80-04 Series
Страница 4: ...4 ACQ80 FW book Page 4 Thursday February 14 2019 11 33 AM ...
Страница 10: ...10 Table of contents ACQ80 FW book Page 10 Thursday February 14 2019 11 33 AM ...
Страница 16: ...16 Introduction to the manual ACQ80 FW book Page 16 Thursday February 14 2019 11 33 AM ...
Страница 26: ...26 Start up control with I O and ID run ACQ80 FW book Page 26 Thursday February 14 2019 11 33 AM ...
Страница 28: ...28 Using the control panel ACQ80 FW book Page 28 Thursday February 14 2019 11 33 AM ...
Страница 54: ...54 Program features ACQ80 FW book Page 54 Thursday February 14 2019 11 33 AM ...
Страница 196: ...196 Additional parameter data ACQ80 FW book Page 196 Thursday February 14 2019 11 33 AM ...
Страница 220: ...220 Fault tracing ACQ80 FW book Page 220 Thursday February 14 2019 11 33 AM ...
Страница 260: ...260 Fieldbus control through a fieldbus adapter ACQ80 FW book Page 260 Thursday February 14 2019 11 33 AM ...
Страница 264: ...264 Parameterization with drive composer ACQ80 FW book Page 264 Thursday February 14 2019 11 33 AM ...
Страница 268: ...268 Parameterization with automation builder drive manager ACQ80 FW book Page 268 Thursday February 14 2019 11 33 AM ...