84 Parameters
12
Configuration of standard analog inputs.
The true readings of the analog inputs can be overridden for
eg. testing purposes. A forced value parameter is provided for
each analog input, and its value is applied whenever the
corresponding bit in this parameter is 1.
Note:
and
) have no effect on forced AI values
(parameters
Note:
Boot and power cycle reset the force selections
(parameters
and
0b0000
0b000...0b1111
Forced values selector for analog inputs AI1 and AI2.
1 = 1
Selects how the drive reacts when an analog input signal
moves out of the minimum and/or maximum limits specified
for the input.
The inputs and the limits to be observed are selected by
parameter
No action
No action taken.
0
Fault
Drive trips on
.
1
Warning
Drive generates an
warning.
2
Last speed
Drive generates a warning (
) and freezes
the speed (or frequency) to the level the drive was operating
at. The speed/frequency is determined on the basis of actual
speed using 850 ms low-pass filtering.
WARNING!
Make sure that it is safe to continue
operation in case of a communication break.
3
Speed ref safe
Not applicable.
Specifies the analog input limits to be supervised. See
parameter
0b0000
0b000...0b1111
Activation of analog input supervision.
1 = 1
Shows value of analog input AI1 in mA or V (depending on
whether the input is set to current or voltage by a hardware
setting).
This parameter is read-only.
0.000
0.000…11.000 V
Value of analog input AI1.
1000 = 1 unit
No.
Name/Value
Description
Def/FbEq16
Bit
Value
0
1 = Force AI1 to value of parameter
1
1 = Force AI2 to value of parameter
2…15
Reserved
Bit
Name
Description
0
AI1 < MIN
1 = Minimum limit supervision of AI1 active.
1
AI1 > MAX
1 = Maximum limit supervision of AI1 active.
2
AI2 < MIN
1 = Minimum limit supervision of AI2 active.
3
AI2 > MAX
1 = Maximum limit supervision of AI2 active.
4…15
Reserved
ACQ80 FW.book Page 84 Thursday, February 14, 2019 11:33 AM
Содержание ACQ80-04 Series
Страница 4: ...4 ACQ80 FW book Page 4 Thursday February 14 2019 11 33 AM ...
Страница 10: ...10 Table of contents ACQ80 FW book Page 10 Thursday February 14 2019 11 33 AM ...
Страница 16: ...16 Introduction to the manual ACQ80 FW book Page 16 Thursday February 14 2019 11 33 AM ...
Страница 26: ...26 Start up control with I O and ID run ACQ80 FW book Page 26 Thursday February 14 2019 11 33 AM ...
Страница 28: ...28 Using the control panel ACQ80 FW book Page 28 Thursday February 14 2019 11 33 AM ...
Страница 54: ...54 Program features ACQ80 FW book Page 54 Thursday February 14 2019 11 33 AM ...
Страница 196: ...196 Additional parameter data ACQ80 FW book Page 196 Thursday February 14 2019 11 33 AM ...
Страница 220: ...220 Fault tracing ACQ80 FW book Page 220 Thursday February 14 2019 11 33 AM ...
Страница 260: ...260 Fieldbus control through a fieldbus adapter ACQ80 FW book Page 260 Thursday February 14 2019 11 33 AM ...
Страница 264: ...264 Parameterization with drive composer ACQ80 FW book Page 264 Thursday February 14 2019 11 33 AM ...
Страница 268: ...268 Parameterization with automation builder drive manager ACQ80 FW book Page 268 Thursday February 14 2019 11 33 AM ...