122 Parameters
1 × Pt100 analog
I/O
Pt100 sensor connected to a standard analog input selected
by parameter
and an analog
output.
The following settings are required:
• Set the hardware jumper or switch related to the analog
input to
U
(voltage). Any change must be validated by a
control unit reboot.
• Set the appropriate analog input unit selection parameter
(volt).
• In parameter group
, set the source
selection parameter of the analog output to
.
The analog output feeds a constant current through the
sensor. As the resistance of the sensor increases along with
its temperature, the voltage over the sensor increases. The
voltage is read by the analog input and converted into
degrees.
5
2 × Pt100 analog
I/O
As selection
, but with two sensors
connected in series. Using multiple sensors improves
measurement accuracy significantly.
6
3 × Pt100 analog
I/O
As selection
, but with three sensors
connected in series. Using multiple sensors improves
measurement accuracy significantly.
7
Direct temperature
The temperature is taken from the source selected by
parameter
. The value of the
source is assumed to be degrees Celsius.
11
Defines the fault limit for temperature supervision function 1.
When measured temperature 1 exceeds the limit, the drive
trips on fault
.
The unit is selected by parameter
.
130 °C or
266 °F
-60…5000 °C or
-76…9032 °F
Fault limit for temperature monitoring function 1.
1 = 1 unit
Defines the warning limit for temperature supervision
function 1. When measured temperature 1 exceeds the limit,
warning
is generated.
The unit is selected by parameter
.
110 °C or
230 °F
-60…5000 °C or
-76…9032 °F
Warning limit for temperature monitoring function 1.
1 = 1 unit
Specifies the analog input when the setting of
requires measurement through an
analog input.
Not selected
None.
0
AI1 actual value
Analog input AI1 on the control unit.
1
AI2 actual value
Analog input AI2 on the control unit.
2
Source selection (see
).
-
Selects the source from which measured temperature 2 is
read.
Usually this source is from a sensor connected to the motor
controlled by the drive, but it could be used to measure and
monitor a temperature from other parts of the process as long
as a suitable sensor is used as per the selection list.
Disabled
None. Temperature monitoring function 2 is disabled.
0
No.
Name/Value
Description
Def/FbEq16
ACQ80 FW.book Page 122 Thursday, February 14, 2019 11:33 AM
Содержание ACQ80-04 Series
Страница 4: ...4 ACQ80 FW book Page 4 Thursday February 14 2019 11 33 AM ...
Страница 10: ...10 Table of contents ACQ80 FW book Page 10 Thursday February 14 2019 11 33 AM ...
Страница 16: ...16 Introduction to the manual ACQ80 FW book Page 16 Thursday February 14 2019 11 33 AM ...
Страница 26: ...26 Start up control with I O and ID run ACQ80 FW book Page 26 Thursday February 14 2019 11 33 AM ...
Страница 28: ...28 Using the control panel ACQ80 FW book Page 28 Thursday February 14 2019 11 33 AM ...
Страница 54: ...54 Program features ACQ80 FW book Page 54 Thursday February 14 2019 11 33 AM ...
Страница 196: ...196 Additional parameter data ACQ80 FW book Page 196 Thursday February 14 2019 11 33 AM ...
Страница 220: ...220 Fault tracing ACQ80 FW book Page 220 Thursday February 14 2019 11 33 AM ...
Страница 260: ...260 Fieldbus control through a fieldbus adapter ACQ80 FW book Page 260 Thursday February 14 2019 11 33 AM ...
Страница 264: ...264 Parameterization with drive composer ACQ80 FW book Page 264 Thursday February 14 2019 11 33 AM ...
Страница 268: ...268 Parameterization with automation builder drive manager ACQ80 FW book Page 268 Thursday February 14 2019 11 33 AM ...