130 Parameters
40
Parameter values for process PID control.
The drive output can be controlled by the process PID. When
the process PID control is enabled, the drive controls the
process feedback to the reference value.
Shows output of the process PID controller.
This parameter is read-only.
-
-200000.00...
200000.00
Process PID controller output.
1 = 1
Shows value of process feedback after source selection,
mathematical function and filtering.
This parameter is read-only.
-
-200000.00...
200000.00
Process feedback.
1 = 1
Shows value of process PID setpoint after source selection,
mathematical function limitation and ramping.
This parameter is read-only.
-
-200000.00...
200000.00
Setpoint for process PID controller.
1 = 1
Shows process PID deviation. By default, this value equals
setpoint - feedback, but deviation can be inverted by
parameter
.
This parameter is read-only.
-
-200000.00...
200000.00
PID deviation.
1 = 1
Shows status information on process PID control.
This parameter is read-only.
0b0000
0b0000…0b1111
Process PID control status word.
1 = 1
No.
Name/Value
Description
Def/FbEq16
Bit
Name
Value
0
PID active
1 = Process PID control active.
1
Setpoint frozen
1 = Process PID setpoint frozen.
2
Output frozen
1 = Process PID controller output frozen.
3
PID sleep mode
1 = Sleep mode active.
4
Sleep boost
1 = Sleep boost active.
5
Reserved
6
Tracking mode
1 = Tracking function active.
7
Output limit high
1 = PID output is being limited by par.
8
Output limit low
1 = PID output is being limited by par.
9
Reserved
10
PID set
0 = Parameter set 1 in use. 1 = Parameter set 2 in use.
11
Reserved
12
Internal setpoint
active
1 = Internal setpoint active (see par.
…
13…15 Reserved
ACQ80 FW.book Page 130 Thursday, February 14, 2019 11:33 AM
Содержание ACQ80-04 Series
Страница 4: ...4 ACQ80 FW book Page 4 Thursday February 14 2019 11 33 AM ...
Страница 10: ...10 Table of contents ACQ80 FW book Page 10 Thursday February 14 2019 11 33 AM ...
Страница 16: ...16 Introduction to the manual ACQ80 FW book Page 16 Thursday February 14 2019 11 33 AM ...
Страница 26: ...26 Start up control with I O and ID run ACQ80 FW book Page 26 Thursday February 14 2019 11 33 AM ...
Страница 28: ...28 Using the control panel ACQ80 FW book Page 28 Thursday February 14 2019 11 33 AM ...
Страница 54: ...54 Program features ACQ80 FW book Page 54 Thursday February 14 2019 11 33 AM ...
Страница 196: ...196 Additional parameter data ACQ80 FW book Page 196 Thursday February 14 2019 11 33 AM ...
Страница 220: ...220 Fault tracing ACQ80 FW book Page 220 Thursday February 14 2019 11 33 AM ...
Страница 260: ...260 Fieldbus control through a fieldbus adapter ACQ80 FW book Page 260 Thursday February 14 2019 11 33 AM ...
Страница 264: ...264 Parameterization with drive composer ACQ80 FW book Page 264 Thursday February 14 2019 11 33 AM ...
Страница 268: ...268 Parameterization with automation builder drive manager ACQ80 FW book Page 268 Thursday February 14 2019 11 33 AM ...