Parameters 161
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
DI6
Digital input DI6 (
, bit 5).
7
Min load current
Enables the dry run protection when the actual load is below
the dry run current limit.
8
on page
-
Defines the dry run current limit. When the actual current
goes below the dry run current limit for a defined time (
the drive considers it as a dry run condition and trips on the
fault,
0.00
0.00...3000.00
Current limit.
100 = 1
Defines the time to monitor dry run current limit. After the
defined time elapses, the drive considers it as dry run
condition and trips on the fault,
.
120.0
1.0...300.0
Run trip monitor time.
10 = 1
Defines the rest time to reset the dry run fault (
). The
drive starts automatically if it receives a start command.
120.0
1.0...18000.0
Dry run reset time.
10 = 1
83
Settings for the pump cleaning sequence.
See section
(page
Displays the status of pump cleaning.
Disabled
Pump cleaning is disabled.
0
Clean pump
Pump cleaning is active.
1
No triggers
configured
Pump cleaning is not active.
2
Waiting for
triggering
Waiting for triggering signal.
3
Displays the pump cleaning progress.
0
0.0...100.0%
Percentage
10 = 1
Displays the cleaning count. Cleaning count increments by
one, when the sequence of cleaning cycles are completed.
For example, if
is set as 3,
the pump cleaning completes after three cycles of reverse
and forward motions of the pump and the cleaning count
changes to 1.
0
0...1000000
Total cleaning count.
1 = 1
Enables/disables the pump cleaning.
Not active
Pump cleaning is not active.
0
Start cleaning now
Starts pump cleaning immediately.
1
DI4
Starts pump cleaning when DI4 goes high.
2
DI5
Starts pump cleaning when DI5 goes high.
3
DI6
Starts pump cleaning when DI6 goes high.
4
No.
Name/Value
Description
Def/FbEq16
ACQ80 FW.book Page 161 Thursday, February 14, 2019 11:33 AM
Содержание ACQ80-04 Series
Страница 4: ...4 ACQ80 FW book Page 4 Thursday February 14 2019 11 33 AM ...
Страница 10: ...10 Table of contents ACQ80 FW book Page 10 Thursday February 14 2019 11 33 AM ...
Страница 16: ...16 Introduction to the manual ACQ80 FW book Page 16 Thursday February 14 2019 11 33 AM ...
Страница 26: ...26 Start up control with I O and ID run ACQ80 FW book Page 26 Thursday February 14 2019 11 33 AM ...
Страница 28: ...28 Using the control panel ACQ80 FW book Page 28 Thursday February 14 2019 11 33 AM ...
Страница 54: ...54 Program features ACQ80 FW book Page 54 Thursday February 14 2019 11 33 AM ...
Страница 196: ...196 Additional parameter data ACQ80 FW book Page 196 Thursday February 14 2019 11 33 AM ...
Страница 220: ...220 Fault tracing ACQ80 FW book Page 220 Thursday February 14 2019 11 33 AM ...
Страница 260: ...260 Fieldbus control through a fieldbus adapter ACQ80 FW book Page 260 Thursday February 14 2019 11 33 AM ...
Страница 264: ...264 Parameterization with drive composer ACQ80 FW book Page 264 Thursday February 14 2019 11 33 AM ...
Страница 268: ...268 Parameterization with automation builder drive manager ACQ80 FW book Page 268 Thursday February 14 2019 11 33 AM ...