162 Parameters
Source selection (see
).
-
Defines the number of cycles performed in cleaning program.
For example, 1 cycle = 1 f 1 reverse step.
3
1...65535
Value range
Defines the speed/frequency step size in pump cleaning.
Cleaning speed step is same for positive and negative
directions.
Note:
If you have disabled the negative rotation direction by
speed limits, the pump cleaning does not operate in the
negative direction.
2400
0...3000 rpm
Cleaning speed/frequency value.
1 = 1 rpm
Defines the time required for the drive to reach cleaning
speed set by parameter
.
3.000
0.000...60.000 s
Time
1 = 1s
Defines the time required for the drive to reach zero speed
from the cleaning speed set by parameter
3.000
0.000...60.000 s
Time
1 = 1s
Defines the pump cleaning time in a cycle when the drive is
running at cleaning speed set by
.
10.000
0.000...1000.000 s
Time
1 = 1s
Defines the cleaning off time when the drive stays at zero
speed between positive and negative pulses and after one
cleaning cycle before starting a new cleaning cycle.
5.000
0.000...1000.000 s
Time
1 = 1s
95
Various hardware-related settings.
Selects the supply voltage range. This parameter is used by
the drive to determine the nominal voltage of the supply
network. The parameter also affects the current ratings and
the DC voltage control functions of the drive.
WARNING!
An incorrect setting may cause the motor
to rush uncontrollably.
Note:
The selections shown depend on the hardware
of the drive. If only one voltage range is valid for the drive in
question, it is selected by default.
Automatic / not
selected
No voltage range selected. The drive will not start modulating
before a range is selected, unless parameter
is set to
, in which case the drive
estimates the supply voltage itself.
0
380…415 V
380…415 V
2
No.
Name/Value
Description
Def/FbEq16
ACQ80 FW.book Page 162 Thursday, February 14, 2019 11:33 AM
Содержание ACQ80-04 Series
Страница 4: ...4 ACQ80 FW book Page 4 Thursday February 14 2019 11 33 AM ...
Страница 10: ...10 Table of contents ACQ80 FW book Page 10 Thursday February 14 2019 11 33 AM ...
Страница 16: ...16 Introduction to the manual ACQ80 FW book Page 16 Thursday February 14 2019 11 33 AM ...
Страница 26: ...26 Start up control with I O and ID run ACQ80 FW book Page 26 Thursday February 14 2019 11 33 AM ...
Страница 28: ...28 Using the control panel ACQ80 FW book Page 28 Thursday February 14 2019 11 33 AM ...
Страница 54: ...54 Program features ACQ80 FW book Page 54 Thursday February 14 2019 11 33 AM ...
Страница 196: ...196 Additional parameter data ACQ80 FW book Page 196 Thursday February 14 2019 11 33 AM ...
Страница 220: ...220 Fault tracing ACQ80 FW book Page 220 Thursday February 14 2019 11 33 AM ...
Страница 260: ...260 Fieldbus control through a fieldbus adapter ACQ80 FW book Page 260 Thursday February 14 2019 11 33 AM ...
Страница 264: ...264 Parameterization with drive composer ACQ80 FW book Page 264 Thursday February 14 2019 11 33 AM ...
Страница 268: ...268 Parameterization with automation builder drive manager ACQ80 FW book Page 268 Thursday February 14 2019 11 33 AM ...