218 Fault tracing
D4B0
Running dry
Dry run protection is activated. Check the pump inlet for sufficient
water level. Check dry run protection
settings in parameter group
.
D4B1
PV max volt
The DC bus voltage in the
inverter is above the voltage
set in
• Check the number of PV cells
connected in series.
• Ensure that voltage is less
than the voltage set in
.
FF61
ID run
Motor ID run was not
completed successfully.
Check the nominal motor values in
parameter group
.
Check that no external control system is
connected to the drive.
Cycle the power to the drive (and its
control unit, if powered separately).
Check that no operation limits prevent
the completion of the ID run. Restore
parameters to default settings and try
again.
Check that the motor shaft is not locked.
0001 Maximum current limit too low.
Check settings of parameters
and
. Make sure that
>
Check that the drive is dimensioned
correctly according to the motor.
0002 Maximum speed limit or
calculated field weakening
point too low.
Check settings of parameters
•
•
•
•
•
Make sure that
•
> (0.55 ×
) >
(0.50 × synchronous speed)
•
< 0, and
• supply voltage > (0.66 ×
0003 Maximum torque limit too low.
, and the torque limits in
group
Make sure that the maximum torque limit
in force is greater than 100%.
0004 Current measurement
calibration did not finish within
reasonable time
Contact your local ABB representative.
0005…0008 Internal error.
Contact your local ABB representative.
0009 (Asynchronous motors only)
Acceleration did not finish
within reasonable time.
Contact your local ABB representative.
Code
(hex)
Fault / Aux. code
(
aux
code visible only on
assistant control panel
and drive composer
)
Cause
What to do
ACQ80 FW.book Page 218 Thursday, February 14, 2019 11:33 AM
Содержание ACQ80-04 Series
Страница 4: ...4 ACQ80 FW book Page 4 Thursday February 14 2019 11 33 AM ...
Страница 10: ...10 Table of contents ACQ80 FW book Page 10 Thursday February 14 2019 11 33 AM ...
Страница 16: ...16 Introduction to the manual ACQ80 FW book Page 16 Thursday February 14 2019 11 33 AM ...
Страница 26: ...26 Start up control with I O and ID run ACQ80 FW book Page 26 Thursday February 14 2019 11 33 AM ...
Страница 28: ...28 Using the control panel ACQ80 FW book Page 28 Thursday February 14 2019 11 33 AM ...
Страница 54: ...54 Program features ACQ80 FW book Page 54 Thursday February 14 2019 11 33 AM ...
Страница 196: ...196 Additional parameter data ACQ80 FW book Page 196 Thursday February 14 2019 11 33 AM ...
Страница 220: ...220 Fault tracing ACQ80 FW book Page 220 Thursday February 14 2019 11 33 AM ...
Страница 260: ...260 Fieldbus control through a fieldbus adapter ACQ80 FW book Page 260 Thursday February 14 2019 11 33 AM ...
Страница 264: ...264 Parameterization with drive composer ACQ80 FW book Page 264 Thursday February 14 2019 11 33 AM ...
Страница 268: ...268 Parameterization with automation builder drive manager ACQ80 FW book Page 268 Thursday February 14 2019 11 33 AM ...