The RDY signal is output when the inverter has no fault, its DC bus
voltage is normal; the Start Prohibit function is disabled. It is ready to
start.
16: Inverter fails
The signal is given if the inverter has faults.
17: Extended function 1 of host
The output signal of terminal Y1 or TC is directly controlled by a serial
port. Refer to the communication protocol of DT100.
19: preset operating time out
The signal is given if the inverter total operating time ( PN.01 )
reaches preset operating time ( PN.00 ) .
P6.04 AO output function
Range: 0
~
12
【
0
】
P6.05~P6.06 Reserved
Reserved
Table 7-9
Setting
Function
Range
0
Output freq. before
compensation
0
~
Max. output freq.
1
Output freq. after
compensation
0
~
Max. output freq.
2
Preset freq.
0
~
Max. output freq.
3
Output current
0
~
2 times of inverter rated current
4
Output current
0
~
2 times of motor rated current
5
Output torque
0
~
2 times of motor torque
6
Output voltage
0
~
1.2 times of inverter rated voltage
7
Bus voltage
0
~
800V
8
Reserved
Reserved
9
AI
0
~
10V/0
~
20mA
10
Output power
0
~
2 times of rated power
11
Extended function 2 of
host
0
~
65535