4. Specifications and Optional Parts
4.1 Specifications
Table 4-1 DT100 Specifications
Item
Description
Input
Rated voltage;
Frequency
DT100-4Txxxxx: 380V
~
440V; 50Hz/60Hz
DT100-2Sxxxxx: 200V
~
240V; 50Hz/60Hz
Permissible
fluctuation range
Voltage contant fluctuate ≤±10%, Transient
fluctuate: -15%
~
+10%, out of balance voltage
rate: ≤3
%
, frequency fluctuation:≤5
%
Output
Rated voltage
DT100-4Txxxxx: 0
~
380V/440V
DT100-2Sxxxxx: 0
~
200V/240V
Frequency
0Hz
~
650Hz
Control
functions
Modulation mode
Flux vector PWM modulation
Speed range
1: 100
Starting torque
180% rated torque at 0.5Hz
Accuracy of speed
at steady state
≤±0.5
%
rated synchronous speed
Torque boost
Auto torque boost, Manual torque boost
Acc/Dec curve
Linear
Jog
Jog frequency, Acc/Dec time,
Jog interval are adjustable
Multi-speed
operation
15 sections of frequency. By the built-in PLC or
terminals.
Closed-loop
control
Analog closed-loop
Auto voltage
regulation
( AVR )
Steady output voltage,
when power network voltage fluctuates.
Auto current
regulation
Current amplitude is regulated
to avoid overcurrent automatically
Auto carrier
regulation
Adjust the carrier frequency automatically,
according to the load characteristics
Special
Internal counter
External pulse signal is counted by X terminal