![A-TS TECHNOLOGY DT100 Series Скачать руководство пользователя страница 90](http://html1.mh-extra.com/html/a-ts-technology/dt100-series/dt100-series_user-manual_447052090.webp)
A-TS
90
https://a-ts.cn/en/
F0 Group: Basic Function Parameters ( total 15 items )
Code
Name
Setting Scope
Min
Unit
Defaulte
d Value
Addres
s
Chang
e
P0.0
9
Max output
frequency
upper limit
frequency ~
650.00Hz
0.01H
z
50.00Hz
009H
×
P0.1
0
Max output
voltage
1
~
480V
1V
Rated
00AH
×
P0.1
1
Running
direction
0: Forward
1: Revserse
1
0
00BH
○
P0.1
2
Acc time 1
0.1
~
3600s
0.1s
6s
00CH
○
P0.1
3
Dec time 1
0.1
~
3600s
0.1s
6s
00DH
○
P0.1
4
Reserved
-
-
-
00EH
*
F1 GROUP: Motor Parameter ( total 11 items )
Code
Name
Setting Scope
Min
Unit
Defaulted
Value
Address
Change
P1.00
Reserved
-
-
-
100H
*
P1.01
Motor
poles
2
~
14
2
4
101H
×
P1.02
Rated
power
0.4
~
1000kW
0.1KW
Power
determination
102H
×
P1.03
Rated
current
0.1
~
6553A
0.1A
Power
determination
103H
×
P1.04
Current
without
load
0.1
~
6553A
0.1A
Power
determination
104H
×
P1.05
Stator
resistance
0.0
~
50.00%
0.01%
Power
determination
105H
○
P1.06
Leakage
inductance
0.0
~
50.00%
0.01%
Power
determination
106H
○