Figure 7-7 Normally-open/close input
In Figure 7-7, X4 is normally open input and X5 normally close input. KM
is external fault relay.
8: Reset
If any of P5.00~P5.04 is set at 8, the inverter can be reset via the terminal
when the inverter has a fault. The function of this terminal is the same
with the RESET key on the keypad.
9~10: External jog command
(
JOGF/JOGR )
If any of P5.00~P5.04 is set at 9~10, the terminal can enable the jog
operation. JOGF is terminal for forward jog operation command and
JOGR is terminal for reverse jog operation command. Jog frequency, jog
interval and jog Acc/Dec time are defined in P9.05~P9.08.
11: Coast to stop
This function is the same with P2.08, however, it is realized by terminal
and convenient for remote control.
12~13: Frequency increase ( UP ) /decrease ( DN )
If the setting is 12~13, the terminal can be used to increase or decrease
frequency instead of
▲and ▼keys on the panel for remote control. This
terminal is valid when P0.00=1 or P0.03=2. Increasing or decreasing rate
is determined by P5.09.
14: Pause command for simple PLC
:
If the setting is 14, the terminal is used to pause the PLC operation and
the inverter operates at zero frequency when the terminal is enabled, but
the running time is not counted. If the terminal is disabled, the inverter will