Bit1
1
Inverter reverse
0
Inverter forward
Bit2
1
Reach main setting
0
Not reach main setting
Bit3
1
Allow commmunciation
control
0
Ban commmunciation
control
Bit7~4
0000B
Reserved
Bit15~8
00~0xFF
Faule code
0: Normal ;
None 0: Fault, Specific
fault codes details
refer to the inverter
user manual
E.g. ,motor overload
F.oL2 will be the fault
code of 0x0E,
undervoltage will be
0x1F.
11.4 Instruction
1, Inverters cannot communicate during the restoring default parameters
and parameter identification phase, after that communication back to be
normal.
2, Inverter internal parameters P1.10, PP.03 cannot be modified through
communication setting.
3, Writing FP. 00 can verify the user password. after the success of the
authentication of password, the host FC gets permission of accessing the
inverter parameters. After finishing the accessing, writing an invalid
password to FP. 00 can shut down the access permissions.
4, The same function setting for Multiple multi-function input terminals
function will cause dysfunction, which situation should be avoided when
users modify multi-function terminal function through the MODBUS
protocol.
Application Examples:
Rewrite the 1 # Inverter operation frequency to be 35.00 HZ ( internally
denote to be 3500 ) , command as follows: