A-TS
72
https://a-ts.cn/en/
DT100 has 29 kinds of alarms. It can memorize the types of 3 latest faults
( PL.14~PL.16 ) , and the voltage, current and frequency
( PL.17~PL.19 ) of the most recent fault.
See chapter 8 for the detailed introductions to the alarm.
7.17 Operation Time and Temperature of Cooling Fan
( PN )
If the accumulated operating time has amount to PN.00, the inverter will
give out an indicating signal. Please refer to P6.00
~
P6.02.
PN.01 is the total accumulated operating time from delivery till now.
PN.02 refers to the temperature of inverter module.
Display range: 0
~
120
℃
; Accuracy: 5
%
.
7.18 Protection of Parameters ( PP )
User password can prevent unauthorized persons from checking and
modifying the parameters.
PL.10~ PL.13 Reserved
Reserved
PL.14 Fault type of the first two times
Range: 0
~
29
【
0
】
PL.15 Fault type of the previous time
Range: 0
~
29
【
0
】
PL.16 Fault type of the last time
Range: 0
~
29
【
0
】
PL.17 Bus voltage at the last fault
Range: 0
~
999V
【
0V
】
PL.18 Output current at the last fault
Range: 0
~
6553A
【
0.0A
】
PL.19 Freq. at the last fault
Range: 0.00
~
650.00Hz
【
0.00Hz
】
PL.20 Heatsink 1 temperature at the last fault
Range: 0.0
~
120.0
℃【
0
℃】
PL.21Reserved
Reserved
PN.00 Preset operation time
Range: 0
~
65.535kh
【
0
】
PN.01 Total operation time
Range: 0
~
65.535kh
【
0
】
PN.02 Temperature of heatsink 1
Range: 0
~
120
℃【
0
】
PN.03 Reversed
Reversed
PP.00 User password
Range: 0000
~
9999
【
0000
】