When the setting is 43, this terminal is used to input counting pulse signal
to the internal counter of the inverter. The max.pulse frequency is 200Hz.
The present counting value can be saved at power off. See P6.10 and
P6.11 for details.
44: Reserved
45: Reserved
P5.08 Terminal control mode
Range: 0
~
3
【
0
】
This parameter defines four operating modes controlled by external
terminals.
0: 2-wire operating mode 1
K1
K2
0
0
1
0
0
1
1
1
Command
Stop
REV
FWD
Stop
Xi
(FWD)
Xi
(REV)
COM
P24
PLC
K2
K1
Figure 7-8 2-Wire Operation Mode 1
1: 2-wire operating mode 2
K1
K2
0
0
0
1
1
0
1
1
Command
Stop
FWD
REV
Stop
Xi
(FWD)
Xi
(REV)
COM
P24
PLC
K2
K1
Figure 7-9 2-Wire Operation Mode 2
2: 3-wire operating mode 1
P24
Xi(REV)
COM
Xi
PLC
Xi(FWD)
SB2
SB1
SB3
Figure 7-10 3-Wire Operation Mode 1