A-TS
9
https://a-ts.cn/en/
During installation:
DANGER
Please install the inverter on the fireproofing material ( such as
metal ) to prevent fire, and keep it away from combustible materials !
Do not loosen the fixed screws of the components.
When you need to install two or more inverters in one cabinet,
cooling fans should be provided,and the installation positions should be
arranged properly to make sure that the ambient temperature is below
45
℃
. Otherwise it could cause fire or damage to the devices.
Install the inverter in places without vibration or direct sunlight.
Do not drop any wire end or screw into the inverter. Failure to
comply will result in damage to the inverter.
At wiring:
DANGER
Wiring must be performed only by qualified personnel under
instructions in this manual. Improper operation may cause unexpected
accidents.
A circuit breaker must be used between the power supply and
inverter to isolate. Otherwise the fire may be caused !
Never wire the inverter unless the power supply is totally cut off !
The ground terminal must be grounded properly by standard to
avoid electrical accident !
Pay attention to the marks of the wiring terminals and ensure
correct wiring. Never connect the power cables to the output terminals
( U,V, W ) of the inverter.Otherwise it will cause damage to the inverter !
The wring must comply with the EMC requirements and safety
standards in the region. Use wire diameter sizes recommended in the
manual, otherwise it may cause an accident !
Use the shielded cable for the encoder, and ensure that the
!
CAUTION
!
CAUTION