9.15
Member MOBUS Master
After addressing, (manual or automatic) the members are then listed to the
“
MODBUS Master
”
menu
group.
Main menu
The function for activation by MODBUS is displayed after the address of the
member.
The same function is programmed initially for all members after addressing.
|
1.
Control Signal (2A)
|
.
I.e. every member is activated by the output of control circuit 1.
MODBUS Master
Fan 1 (2A)
Fan 2 (2A)
Fan 3 (2A)
[P] Enter
[ESC] Info
After selection with the
▼
▲
keys, press the
P-key
to open the State menu of the member (menu
content depends on the type of member).
State menu member
Example: ECblue fan
Fan 1 (2A)
ECblue V13.05
←
Device type and
fi
rmware version
Fan OK!
←
Operating state of the member
Speed [rpm 570]
←
Speed Actual value (1/min)
Motorcurrent [A] 2.60
←
Current consumption
P=0W
Level=0%
←
Power consumption and modulation of the device
[P] Edit
[ESC] Menu
To set the MODBUS function for the member, press the
P-key
.
Fan 1 (2A)
Press the P-key
to open the menu.
Select the desired MODBUS function with the
▼
▲
keys and save with the
P-key
.
Pre-programmed function
|
1. Control Signal (2A)
|
= output of control circuit 1.
For example, to activate speed controllers for fans or fans with integrated con-
troller and MODBUS interface.
The programmable functions correspond to the functions for the analogue outputs
(
IO Setup).
•
For members activated by control circuit 2, function:
|
2. Control Signal (8A)
|
•
For members activated in groups (function:
|
5A
|
,
|
11A
|
,
|
12A
|
), the
“
Group
Version
”
setting must be observed, at factory setting
“
OFF
”
there is no
activation (
Controller Setup)!
1. Control signal
(2A)
MB Function
[P] Edit
[ESC] Menu
Exit the menu with the Esc key combination
▼
+
▲
.
Operating Instructions
UNIcon MODBUS Master
Programming
L-BAL-E207-GB 1723 Index 003
Part.-No.
92/114