Limits
E1 Delay
Time delay exceeding
“
Modulation max.
”
up to indication by relay and alarm symbol.
Setting range: 0 - 120 sec.
Factory setting: 2 sec.
- - - - -
Lmt E1Del.
Information
Always adjust the value for the maximum input signal higher than the value for the minimum input
signal!
E1 Max. > E1 Min.
Example for a limit indication of default signal or sensor signal to
“
Analog In 1
”
50 %
Analog IN
0
1
100 %
1
11.05.2007
v_grenzwert_signal_k1_1.vsd
Settings:
- E1 Max.: 80 %
- E1 Min.: OFF
- switching hysteresis 5 % (from
100 %)
50 %
Analog IN
0
1
100 %
2
11.05.2007
v_grenzwert_signal_k1_2.vsd
Settings:
- E1 Min.: 20 %
- E1 Max.: OFF
- switching hysteresis 5 % (from
100 %)
50 %
Analog IN
0
1
100 %
3
11.05.2007
v_grenzwert_signal_k1_3.vsd
Settings:
- E1 Min.: 20 %
- E1 Max.: 80 %
- switching hysteresis 5 % (from
100 %)
Terminal
“
E1
”
and
“
GND
”
alarm via relay
“
K1
”
(non-inverted) IO Setup
→
K1 function:
|
5 K
|
= limit
indicators
Operating Instructions
UNIcon MODBUS Master
Programming
L-BAL-E207-GB 1723 Index 003
Part.-No.
81/114