100 %
Max. Speed
Base setup
Manual mode
“
OFF
”
= automatic control as function of the set parameters (Factory setting)
“
ON
”
= automatic control without function, speed setting in menu
“
Speed manual
”
OFF
Manual mode
Base setup
Speed manual
Manual speed setting without in
fl
uence by the external signal.
Activation by menu
“
Manual mode
”
or external contact at digital input (
IO Setup).
Setting range: 0...100 %
“
Min. Speed
”
...
“
Max. Speed
”
Factory setting: 100 %
For information about deactivated regulation the adjusted value for manual speed is
indicated alternating with the actual value.
100 %
Speed manual
9.7
Menu group Start
Main menu
Start
Start
Settings
Protocol
Base setup
Controller Setup
Start
PIN input
The service menu for the installation can be protected against unintentional changes
by a pin code. With further pin codes putting back to pre-setting is possible.
PIN 0010
Opening service menu, if PIN-protection activated.
PIN 1234
Freischalten Menu group
“
Setting
”
.
if
“
set protection
”
=
“
ON
”
(
Controller Setup)
PIN 9090
Restore user setting.
PIN 9091
Save user setting (corresponds function
“
Save user setup
”
=
“
ON
”
Controller Setup)
PIN 9095
Restore factory setting = delivery status
Exception:
The stored events in the
“
Protocol
”
menu are retained after resetting to factory setting!
- - - - -
PIN input
Start
Language
Menu language by the factory set to English.
In this menu different national languages can be selected (GB = English, D = German
...).
GB
Language
Operating Instructions
UNIcon MODBUS Master
Programming
L-BAL-E207-GB 1723 Index 003