9
Programming
Display in SI units or Imperial units (US)
The following description is for display in SI units (factory setting). The appropriate conversion factors
must be observed when switching over to Imperial units (US) (
menu group Start / US Units).
9.1
Speed controller
1.01
,
1.02
9.1.1
Speed controller with setting by external signal
1.01
Settings for controller output with function
|
2A
|
(by analogue signal
IO Setup, by MODBUS
members menu).
Base setup
1.01
Main menu
Base setup
Setting
Protocol
Base setup
Controller Setup
IO Setup
Base setup
Mode
Factory setting Mode:
1.01
1.01
Mode
Base setup
E1 Analog In
Selection: 0 - 10V, 0 - 20 mA, 4 - 20 mA (Inverting, E1 BUS Modus
IO Setup)
Factory setting: 0 - 10 V
0 - 10V
E1 Analog In
Base setup
E2 Function
(only for special applications)
Analog input 2
“
E2
”
factory set at
“
OFF
”
.
For operation with a second setting signal and switch over by potential-free contact: E2
Function = Ext. Setpoint (1E)
Necessary function for digital input: E1/E2 (4D)
IO Setup
For operation with a second signal and automatic control at the higher level: E2
Function = comparison E1 (4E).
OFF
E2 Function
Base setup
E2 Analog In
Display as long as no function allocated:
|
- - - - -
|
Selection: 0 - 10 V, 0 - 20 mA, 4 - 20 mA (Inverting, E2 BUS Modus
IO Setup)
Factory setting: 0 - 10 V
- - - - -
E2 Analog In
Setting for operation
1.01
Main menu
Setting
Setting
Protocol
Base setup
Controller Setup
IO Setup
Operating Instructions
UNIcon MODBUS Master
Programming
L-BAL-E207-GB 1723 Index 003
Part.-No.
27/114