
Controller Setup
D-component
More
“
D-component
”
causes more stability by a clean actual value signal with shorter
correction times
By a actual value signal with a superposition should be done to attitude without
“
D-
component
”
→
0 %
Setting range: 0 - 200 %
value smaller = less
“
D-component
”
value higher = more
“
D-component
”
50 %
KD
Controller Setup
Integration time = correction time
Setting range: 0 - 200 %
smaller = faster
bigger = more slowly
0 %
TI
9.9.9
Group control
Fan groups can be activated by the analogue outputs
“
A1
”
and
“
A2
”
, the relay outputs
“
K1
”
and
“
K2
”
or
by the RS-485 interface for MODBUS RTU.
Controller Setup
Setting range 0 / 1
Following group versions are available:
•
0
: One controlled group and up to three switched groups (factory setting)
•
1
: Two controlled groups
0
Group version
Group control via analogue outputs and relays
•
The groups must be connected at the appropriate programmed output when activating by the
analogue outputs and relays.
•
The assignment of the analogue outputs and the relays for the group control takes place in the IO
Setup.
•
The number of possible groups depends on the available hardware outputs in the MODBUS Master
(maximum of 4 groups possible).
Group control im MODBUS Master Operation
•
If controlling via MODBUS, an individual function can be programmed for each group device.
•
The virtual outputs are assigned after the menu group
“
MODBUS Master
”
for the respective
component
“
fan 1
”
..
“
fan xx
”
.
•
The number of possible groups does
not depend
on the available hardware outputs in the
MODBUS Master (maximum of 4 groups possible).
Group functions (
IO Setup)
Analog output A1, A2
|
2A
|
= Group 1
MODBUS A1, A2
|
5A
|
= Group 2
|
11A
|
= Group 3
|
12A
|
= Group 4
Relay output K1, K2
|
8K
|
= Group 2
|
12K
|
= Group 3
|
13K
|
= Group 4
Operating Instructions
UNIcon MODBUS Master
Programming
L-BAL-E207-GB 1723 Index 003
Part.-No.
57/114