9.2.2
Settings for operation modes
2.01
...
2.05
2.01
Temperature control airconditioning and refrigeration
(preset set-point 20.0
°
C, P-band 5.0 K)
2.02
Temperature control depending on outdoor temperature
(preset set-point 5.0
°
C, - P-band 20.0 K)
2.03
Temperature control with pre-programmed additional functions (heating, shutter, temperature monitor-
ing).
2.04
Temperature control with 2 sensors
Comparison with control to higher value
“
E2 Function
”
set to comparison
|
4E
|
. Display during
operation:
“
Control value
”
Alternative: Average calculation of 2 measuring places
“
E2 Function
”
set to
|
3E
|
. Display during
operation:
“
Average E1 / E2
”
2.05
Temperature control with 2 sensors, regulation on difference temperature.
Display during operation:
“
Value of E1 - E2
”
in K,
“
E1
”
= reference temperatur,
“
E2
”
causes positiv (E2
< E1) or negative (E2 >E 1) difference.
Settings for controller output with function
|
2A
|
(by analogue signal
IO Setup, by MODBUS
members menu).
Main menu
Setting
Setting
Protocol
Base setup
Controller Setup
IO Setup
Setting
Setpoint1
Setting range with passive sensor type
“
TF
”
,
“
PT1000
”
: -50.0...150.0
°
C
Factory setting:
2.01
,
2.03
,
2.04
: 20.0
°
C
at
2.02
: 5.0
°
C
at
2.05
: 0.0
°
C
Setting range with passive sensor type
“
MTG-120V
”
: -10.0
°
C...+120.0
°
C
Factory setting
2.01
-
2.05
: 55.0
°
C
20.0
°
C
Setpoint1
Setting
Setpoint2
Setting
“
Setpoint 2
”
e.g. reduced value for night operation.
Switch over Setpoint 1/2 by external contact (display as long as no allocation is carried
out:
|
- - - - -
|
IO Setup).
- - - - -
Setpoint2
Setting
Pband
Narrow control range = Short control times
Wide control range = Longer control times and more stable control
Passive sensor type
“
TF
”
,
“
PT1000
”
Setting range: 0 - 200.0 K (Kelvin)
Factory setting: 5.0 K, (at
2.02
: 20.0 K)
active Sensor type
“
MTG-120V
”
Setting range: -10.0...+120.0 K
Factory setting: 65.0 K
5.0 K
Pband
Setting
Min. Speed
Setting range: 0...
“
Max. Speed
”
Factory setting: 0 %
0 %
Min. Speed
Setting
Max. Speed
Setting range: 100 %...
“
Min. Speed
”
Factory setting: 100 %
100 %
Max. Speed
Operating Instructions
UNIcon MODBUS Master
Programming
L-BAL-E207-GB 1723 Index 003
Part.-No.
33/114