
Setting
Setpoint2
Setting
“
Setpoint 2
”
e.g. reduced value for night operation.
Switch over Setpoint 1/2 by external contact (display as long as no allocation is carried
out:
|
- - - - -
|
IO Setup).
- - - - -
Setpoint2
Setting
Pband
Narrow control range = Short control times
Wide control range = Longer control times and more stable control
3.01
and
3.03
Setting range: in measuring range of sensor
Factory setting: 5.0 bar
3.02
and
3.04
Setting range: dependent on the selected refrigerant
Factory setting: 7.0 K
5.00 bar
Pband
Setting
Min. Speed
Setting range: 0...
“
Max. Speed
”
Factory setting: 0 %
0 %
Min. Speed
Setting
Max. Speed
Setting range: 100 %...
“
Min. Speed
”
Factory setting: 100 %
100 %
Max. Speed
Setting
Manual mode
“
OFF
”
= automatic control as function of the set parameters (Factory setting)
“
ON
”
= automatic control without function, speed setting in menu
“
Speed manual
”
OFF
Manual mode
Setting
Speed manual
Manual speed setting without in
fl
uence by the external signal.
Activation by menu
“
Manual mode
”
or external contact at digital input (
IO Setup).
Setting range: 0...100 %
“
Min. Speed
”
...
“
Max. Speed
”
Factory setting: 100 %
For information about deactivated regulation the adjusted value for manual speed is
indicated alternating with the actual value.
100 %
Speed manual
Operating Instructions
UNIcon MODBUS Master
Programming
L-BAL-E207-GB 1723 Index 003
Part.-No.
40/114