Setting
Min. Speed
Setting range: 0...
“
Max. Speed
”
Factory setting: 0 %
0 %
Min. Speed
Setting
Max. Speed
Setting range: 100 % -
“
Min. Speed
”
Factory setting: 100 %
100 %
Max. Speed
Setting in operation
1.02
After installation is completed, only the
“
Setting direct
”
or
“
Setting Step
”
setting is visible in the
“
Info
”
menu
group. All other menus are protected by a PIN.
Info
Setting direct
(at Number steps: 0
“
Base setup
”
)
Setting range: Min. Speed - Max. Speed
Factory setting: 80 %
76 %
Setting direct
The value set by the
▼
▲
keys is accepted and executed directly (
P
key without
function).
Info
Setting step
(at Number steps: 1 - 5
“
Base setup
”
)
Setting range: 0 - programmed number steps
Factory setting: 0
5
Setting Step
Switching over to the protected
“
Info
”
menu group takes place automatically after approximately 15
minutes if no key is pressed.
Possibilities for early activation of PIN protection:
•
Select the
“
Info
”
menu group and con
fi
rm with the
P
key.
•
Press the
|
Esc
|
key combination several times until the
“
Setting direct
”
or
“
Setting Step
”
menu is
displayed.
•
Execute the
“
Reset
”
function in the
“
Start
”
menu group.
•
By switching the mains voltage off and then on again.
Input PIN
|
0010
|
to exit the protected area
→
→
→
→
→
76 %
Setting direct
▼
+
▲
=
|
Esc
|
- - - - -
PIN input
P
0010
PIN input
P
Start
Setting
Protocol
Base setup
Controller Setup
IO Setup
5
Setting Step
adjust PIN 0010
Operating Instructions
UNIcon MODBUS Master
Programming
L-BAL-E207-GB 1723 Index 003