Information
By entering the
“
PIN 9095
”
in the
“
PIN
”
menu of the
“
Start
”
menu group the device is reset to the as-
delivered state (except for the saved events in the
“
Protocol
”
menu).
Any changes that have been made to the settings are thus lost.
9.9.4
Sensor Alarm ON / OFF
The inputs
“
E1 Analogue In
”
and if Sensor 2 is activated
“
E2 Analogue In
”
are monitored.
In case of an interruption or short-circuit in the sensor conductor, or in case of measured values that
lie outside of the device
’
s measurement range, a time-delayed fault indication takes place.
Function only in controller mode (from
2.01
)!
Controller Setup
With
“
Alarm Sensors
”
=
“
ON
”
(factory setting). Indicated
sensor disturbances are displayed as
“
Alarm
”
alternating to
the actual value and stored in the menu of
“
Protocol
”
.
A programmed alarm relay (factory setting relay K2) indicates
the sensor failure.
Sensor 1
ON
Alarm sensors
Controller Setup
With
“
AlarmSensors
”
=
“
OFF
”
areindicated sensor disturban-
ces as
“
Message
”
alternating to the actual value and stored in
the menu of
“
Protocol
”
.
Sensor 1
OFF
Alarm sensors
9.9.5
Limit
Controller Setup
After allocation of a digital input (
IO Setup) an adjustable limitation of the modulation
can be activated via a digital input (
“
D1
”
,
“
D2
”
, ..).
Display as long as no allocation has been carried out in
“
IO Setup
”
:
|
- - - -
|
The limitation in
fl
uences both outputs in operation with two control circuits.
- - - - -
Limit
“
Limit value
”
= max. possible modulation (e.g.
speed reduction during night operation by
time switch).
Setting range:
“
Limit
”
=
“
Min. Speed
”
to
“
Max.
Speed
”
.
Factory setting: 100 %
max. modulation, i.
e. no limit.
Setting depending on device tye in: % or rpm.
D
P
Min.
L= 70% Min.= 0 % Max. = 100 %
50 %
R
0 %
I
S
100 %
I
L
L = 70% Min. = 35 % Max. = 85 %
28.03.2013
v_limit_cxe_master.vsd
80
70
60
50
40
30
20
10
90
A
n
a
lo
g
O
u
t
[V
]
1
2
3
4
5
6
7
8
9
1
0
M
O
D
B
U
S
O
u
t
[%
]
100
Limit (idealized principle diagram)
MODBUS Out:
speed setting over MODBUS
Analog Out:
speed setting over analog output 0 - 10 V
L
Limit
S
Setpoint
R
Pband
D
Speed controller: setting signal
P
P-controller: control deviation
Operating Instructions
UNIcon MODBUS Master
Programming
L-BAL-E207-GB 1723 Index 003
Part.-No.