Setting
Min. Setpoint
Minimum pressure for very low outside temperature
Setting range: depending on measuring range of sensor and
“
K factor
”
Factory setting: 700 m
3
/h
700 m
3
h
Min. Setpoint
9.6
Air velocity control
6.01
9.6.1
Base setup
6.01
Main menu
Base setup
Start
Setting
Protocol
Base setup
Controller Setup
Base setup
Mode
Mode selection
6.01
6.01
Mode
Base setup
E1 Analog In
The sensor input is factory set for mode
6.01
to sensor type
“
MAL1
”
.
Measuring range: 0...1 m/s
Output signal: 0 - 10 V
Connection terminals:
“
E1
”
,
“
GND
”
,
“
24V
”
Other settable sensors / measuring ranges:
•
MAL10 (0...10 m/s, output signal 0 - 10 V)
•
MAL15 * (0...15 m/s, output signal 0 - 10 V)
•
MAL20 * (0...20 m/s, output signal 0 - 10 V)
•
0 - 10 V, 0 - 20 mA, 4 - 20 mA (for sensors with free measuring range and linear
characteristic)
The sensor measuring range must be entered for sensors with free measuring range in
order to display the actual value correctly.
Example 0 - 10 V sensor and measuring range 0 - 5 M/s:
E1 Analog In = 0 - 10 V, E1 Unit = m/s, E1 Decimals = 1, E1 Min. = 0,0 m/s, E1 Max. =
5 m/s
* Alternative measuring ranges which can be selected by jumpers for sensor type
MAL10.
MAL1
E1 Analog In
Base setup
E1 Offset
Sensor calibration with calibrated comparison device.
The current
“
E1 Actual
”
is displayed including the offset set here.
0.00 m/s
E1 Offset
Base setup
E1 Setpoint min
(function depending on the software version available)
Limitation of the adjustable setpoint (see settings for operation)
Setting range: in measuring range of sensor
Factory setting: minimum measurement value
0.00 m/s
E1 Setpoint min
Base setup
E1 Setpoint max
(function depending on the software version available)
Limitation of the adjustable setpoint (see settings for operation)
Setting range: in measuring range of sensor
Factory setting: maximum measurement value
1.00 m/s
E1 Setpoint max