Example for Mode
“
1.01
”
with speed setting signal 0 - 10 V
n [%]
Si E
0
1
2
3
4
5
6
7
8
9
10
0 – 10 V
12.10.2009
v_e1_modus_1_prz.vsd
1
Modus 1
E1 min. = 0 %, E1 max. = 100 %
100
2
E1 min. = 25 %, E1 max. = 100 %
80
60
40
20
3
E1 min. = 20 %, E1 max. = 80 %
E1 min. = 0 %, E1 max. = 80 %
4
Modus 1
Example:
“
E1 min.
”
= 20 %
The controller begins only at approx. 20% higher
signal with minimal modulation.
Example:
“
E1 max.
”
= 80 %
The modulation rises linear to 100% modulation
with 80% setting signal.
Si E
0
1
2
3
4
5
6
7
8
9
10
0 – 10 V
12.10.2009
v_e1_modus_2_prz.vsd
1
Modus 2
E1 min. = 0 %, E1 max. = 100 %
100
2
E1 min. = 40 %, E1 max. = 100 %
80
60
40
20
3
E1 min. = 30 %, E1 max. = 90 %
E1 min. = 0 %, E1 max. = 80 %
4
n [%]
Modus 2
Example:
“
E1 min.
”
= 30 %
Only with approx. 30 % setting signal the controller
begins with approx. 30% modulation.
Example:
“
E1 max.
”
= 80 %
Over 80 % setting signal the modulation is switched
to 100 % modulation.
Si E
0
1
2
3
4
5
6
7
8
9
10
0 – 10 V
12.10.2009
v_e1_modus_3_prz.vsd
1
Modus 3
E1 min. = 0 %, E1 max. = 100 %
100
2
80
60
40
20
3
E1 min. = 30 %, E1 max. = 80 %
E1 min. = 0 %, E1 max. = 80 %
E1 min. = 20 %, E1 max. = 100 %
n [%]
Modus 3
Example:
“
E1 min.
”
= 30 %,
“
E1 max.
”
= 80 %
Over approx. 80 % setting signal the modulation is
switched on.
Below approx. 30 % setting signal the modulation
is switched off.
For a correct function: E1 min. higher 0 % and E1
max. below 100 %.
example 2 and 3 only for information.
Idealized principle diagrams for setting:
“
Min. Speed
”
= 0 % and
“
Max. Speed
”
= 100 %
Operating Instructions
UNIcon MODBUS Master
Programming
L-BAL-E207-GB 1723 Index 003
Part.-No.
75/114