Base setup
E1 Setpoint min
(function depending on the software version available)
Limitation of the adjustable setpoint (see settings for operation)
Setting range: in measuring range of sensor
Factory setting: minimum measurement value
0 m
3
/h
E1 Setpoint min
Base setup
E1 Setpoint max
(function depending on the software version available)
Limitation of the adjustable setpoint (see settings for operation)
Setting range: in measuring range of sensor
Factory setting: maximum measurement value
1060 m
3
/h
E1 Setpoint max
Base setup
E2 Function
The second signal input is not activated at the factory for modes with one sensor.
The function is automatically jointly programmed in operating modes using two sen-
sors. The second analog input is thus allocated and additional function allocations are
not possible.
Modes with two sensors
•
For
5.02
E2 Function at
|
6E
|
preprogrammed = sensor for setpoint lowering.
Preprogrammed sensor type
“
TF..
”
Adjustable
“
E2 function
”
for modes with one sensor
•
|
1E
|
= external setpoint e.g. by external signal (0 - 10 V) instead of setting
“
Setpoint
1
”
. 0 - 10 V
0 - 100 % setting range.
•
|
2E
|
= External manual operation via external signal (0 - 10 V). Switch over
between settings on the device and external manual operation via digital input (
IO Setup: function
|
7D
|
).
•
|
3E
|
= Sensor average to E1
•
|
4E
|
= Sensor comparison to E1
•
|
5E
|
= Sensor difference to E1
•
|
7E
|
= Measurement value = Measurement value e.g. for limit indication, display in
Info menu
“
E2 Actual
”
.
•
|
8E
|
...
|
13E
|
= sensor input for control circuit 2
base setup / operation
with second control circuit.
OFF
E2 Function
9.5.2
Setting for operation modes
5.01
...
5.02
5.01
Volume control, Setpoint in m
3
/h
5.02
Volume control for ventilation systems setpoint depending on outdoor temperature
Settings for controller output with function
|
2A
|
(by analogue signal
IO Setup, by MODBUS
members menu).
Main menu
Setting
Start
Setting
Protocol
Base setup
Controller Setup
Setting
Setpoint1
Setting Setpoint in m
3
/h
Setting range: depending on measuring range of sensor and
“
K factor
”
Factory setting: 530 m
3
/h
530 m
3
h
Setpoint1
Setting
Setpoint2
Setting
“
Setpoint 2
”
e.g. reduced value for night operation.
Switch over Setpoint 1/2 by external contact (display as long as no allocation is carried
out:
|
- - - - -
|
IO Setup).
- - - - -
Setpoint2
Operating Instructions
UNIcon MODBUS Master
Programming
L-BAL-E207-GB 1723 Index 003
Part.-No.
46/114