13.2
Connection diagram
UNIcon CXE/AV(E), CXG-24AV(E)
K1
K2
MCRE17K0
05.12.2012
Netz
Line
N
(-)
L1
(+)
PE
GND
24V
GND
ID
D2
D1
A2
A1
GND
GND
E2
E1
Ausgänge
Outputs
0...10 V
(R
L
> 5 kΩ)
+
3
+
2
1
Digital
In 1/2
Analog
Out 1/2
Analog
In 1/2
24 V DC
Out
Eingänge
Inputs
0...10 V
0...20 mA
4...20 mA
+
4
+
11
14
12
21
24
22
Kontaktbelastung
Contact rating
max. AC 250 V 2 A
5
N
L1
PE
1 ~ 230 V 50/60 Hz
CXE/AV(E)
L2
L1
PE
2 ~ 400 V 50/60 Hz
CXE/AV(E)
+
DC 24 V
CXG-24AV(E)
T
T
2A
(2D+)
2B
(2D-)
1A
(1D+)
1B
(1D-)
GND
MODBUS
Master
(RS-485)
MODBUS
Slave
(RS-485)
q
TF..
KTY 81-210
PT 1000
Digitale
Eingänge
für
potenzialfreie
Kontakte
Digital inputs
for potential
free contacts
J1
USB
6
TF
In 1/2
Ad
d
re
ssi
n
g
1
Line
2
Digital inputs for potential-free contacts
3
Outputs (I
max
= 2 mA): A1 pre-programmed control output e.g. for controlling a speed controller. Fans with integrated controller and input 0 -
10 V can be activated directly. A2 pre-programmed for constant v10 V
4
Inputs E1 + E2: 0...10 V, 0...20 mA, 4...20 mA, TF.. (KTY, Pt1000)
5
Contact rating max. AC 250 V 2 A (ohmic load)
6
Jumper J1 for USB interface (Bootloader)
Attention!
Plug the jumper J1
to both PINs only for a software update via USB interface. The device will not switch on if this jumper is
plugged to both PINs!
Do not replug the jumper under voltage, observe the safety instructions!
0 - 10 V
TF..
DSG 0 - 10 V
MAL 0 - 10 V
MBG..-I
19.09.2012
v_sensoren_e1_t1_anschlplan.vsd
0 - 10 V
10 k
A1
E1
E1
T
T
K
T
Y
8
1
-2
1
0
P
T
1
0
0
0
24V
GND
E1
3
1
BN
GN
MBG..
(4 - 20 mA)
24V
GND
E1
DSG..
(0 - 10 V)
BN
YE
WH
24V
GND
E1
MAL1/10
(0 - 10 V)
1
3
2
GND
Operating Instructions
UNIcon MODBUS Master
Enclosure
L-BAL-E207-GB 1723 Index 003
Part.-No.
111/114