9.9
Controller Setup
9.9.1
PIN protection activate, PIN0010
Controller Setup
The adjustments for the installation in the service level can be protected against
unintentional modi
fi
cations. To do this, activate the
“
PIN protection
”
=
“
ON
”
.
In order to simplify the initial start-up operation, the service level in the factory setting is
free =
“
OFF
”
i.e. accessible without
PIN 0010
.
OFF
PIN Protection
Available menu groups with activated PIN-protection
Main menu
Start
Setting
Protocol
If PIN-protection is switched on, it automatically becomes active after about 15 minutes without keys
being pressed.
Possibilities for early activation of PIN protection:
•
Execute the
“
Reset
”
function in the
“
Start
”
menu group.
•
By switching the mains voltage off and then on again.
Information
After installation of the device has been carried out,
“
PIN-Protection
”
should be activated =
“
ON
”
9.9.2
Set protection activate, PIN 1234
Controller Setup
The
“
Settings
”
menu for the user
’
s basic settings (Setpoint, default value, min, max ..)
are freely accessible when using the factory settings (i.e. without
“
PIN
”
).
If necessary, these can also be protected against unauthorized modi
fi
cations by using
a
“
PIN 1234
”
. For this, the settings protection must be programmed to
“
ON
”
. The
settings menu is then no longer visible without inputting a PIN!
Function only in combination with activated PIN-Protection!
OFF
Set protection
Available menu groups with activated PIN-prot setting protection
Menu
Start
Protocol
9.9.3
Save user settings restore with PIN 9090
Controller Setup
The individually made device con
fi
gurations (User Setting) can be saved here (corre-
sponds to PIN 9091).
By entering
PIN 9090
the individually made device con
fi
gurations can be reestablished
(
Start - PIN Input).
A
fi
le (userconf.csv) is generated and saved on the main drive (root directory) when
saving the user setting.
The data can be accessed via the
ZAset
program.
OFF
Save User Setup
Operating Instructions
UNIcon MODBUS Master
Programming
L-BAL-E207-GB 1723 Index 003
Part.-No.
53/114