Digital inputs D1 and D2
Function
Description
OFF
no function (factory setting)
Enable
(1D)
Enable (remote control)
“
ON
”
/
“
OFF
”
External error
(2D)
External alarm indication
Limit
(3D)
“
Limit
”
ON / OFF
In
fl
uences control circuit 1 and control circuit 2
E1 / E2
(4D)
Switch over input
“
E1
”
/
“
E2
”
(for operation with one control circuit)
Reset
(10D)
Complete re-start of the device
Max. Speed
(11D)
Setting Max. Speed
“
ON
”
/
“
OFF
”
In
fl
uences the respectively set value
“
1. Max. Speed
”
and
“
2. Max. Speed
”
in operation
with two control circuits.
Override Time
(21D)
Overwrite timer function (in operation with timer)
For Mode Speed controller
1.01
Setpoint1/2
(5D)
Switch over
“
Set Intern1
”
/
“
Set Intern2
”
“
Setting External 1
”
must be at
“
OFF
”
.
Setpoint int./ext.
(6D)
Switch over
“
Intern
”
/
“
Extern
”
For modes as controller higher
2.01
Setpoint1/2
(5D)
Switch over
“
Setpoint 1
”
/
“
Setpoint 2
”
for control circuit1
Setpoint int./ext.
(6D)
Switch over
“
Intern
”
/
“
Extern
”
Possible only for operation with one control circuit!
Control/Manual
(7D)
Switch over
“
automatic control
”
/
“
Speed manual
”
Possible only for operation with one control circuit!
Heating/Cooling
(8D)
Switch over control function (e.g.
“
heating
”
/
“
cooling
”
)
1.Setp+Pband1/2
(15D)
for control circuit 1: Switch over Setpoint 1/2 and Pband 1/1
When programming this function,
“
Setting
”
additionally lists the parameter:
“
1.Pband 1.
for control circuit 1
”
Only active in operation with a second control circuit
E1 / E2
(4D)
The output for control circuit 2 is set additionally to
“
A2
”
to
“
A1
”
(regardless of the
programmed function for
|
A1
|
). The
fi
rst control circuit has no output for the duration of
the switch over.
The switch over input
“
E1
”
/
“
E2
”
as in operation with one control circuit is no longer
possible.
2. Setpoint 1/2
(9D)
for control circuit 2: Switch over
“
Setpoint 1
”
/
“
Setpoint 2
”
2.Setp+Pband1/2
(16D)
for control circuit 2: Switch over Setpoint 1/2 and Pband 1/2
When programming this function,
“
Setting
”
additionally lists the parameter:
“
2.Pband 2
for control circuit 2
”
Operating Instructions
UNIcon MODBUS Master
L-BAL-E207-GB 1723 Index 003
Part.-No.
101/114