9.12.5
Inverting timer function
Inverting of the timer function is possible if required.
Timer
Timer Inverting
In the
“
OFF
”
setting (factory setting), the programmed function is activated at the
switch-on time (clock icon in the display) and deactivated again at the switch-off time
(
timer function).
In the
“
ON
”
setting, the programmed function is deactivated at the switch-on time and
activated again at the switch-off time (clock icon in the display).
OFF
Timer Inverting
9.12.6
Overwrite timer function
The timer output can be overwritten for a settable time with a selectable status if required. Activation is
by a digital input (
IO Setup function
|
21D
|
)
Application: Exceptions from the normal timing operation, e.g. for manual or automatic presence
switch, party mode, etc.
Timer
Override Time
Settable time for overwriting the timer function
Setting range: 0...65535 min.
Factory setting: 120 min
In the
“
0 min.
”
setting, the timer function is overwritten with the selected status until the
next timing change.
120
min
Override Time
Timer
Override Status
Settable status when overwriting the timer function:
ON = function as for timer ON
timer function
OFF = function as for timer OFF (factory setting)
OFF
Override Status
9.12.7
Adjustment of the real time clock
Timer
Fine adjustment of the real time clock is possible if required.
The greater the value, the slower the clock runs. If the value is increased by one point,
this corresponds to a slowing of the clock by approx. 2 to 3 s per month.
Setting range: 0 - 127
Factory setting: 60
60
RTC Adjust