MAXinBOX FC 0-10V VALVE
http://www.zennio.com
Technical Support:
http://zennioenglish.zendesk.com
37
SPEED CONTROL CONFIGURATION
Fan Control Mode
: sets if the fan speed will be controllable in “Automatic”,
“Manual” or “AuManual” mode.
In the latter case, the initial mode after the device start-up is automatic.
Moreover, the one-bit object “
[FCV1] Fan: Manual/Automatic
” will permit
switching the mode any time (value “0” for automatic and value “1” for
manual), while “
[FCV1] Fan: Manual/Automatic (Status)
” will inform the bus
whenever the mode changes.
Period of Time to Return to Auto Mode
: sets the time (from 0 to 1440
minutes or from 0 to 24 hours) after which, if no manual speed orders have
been received, the fan control mode will switch back to automatic. The value
“0” leaves this function disabled.
Switch to Manual Mode After Receiving a Manual Control Order
: sets
whether the arrival of a manual fan speed order while in the automatic mode
should switch the fan control to manual or not.
Note
:
this parameter remains hidden unless at least one speed control object
has been enabled. Please, read below.
Return to Auto Mode After Cooling/Heating Mode Switch
: sets whether
the arrival of a cooling/heating mode switch order should activate the
automatic fan speed control, in case of being in manual mode.
SPEED THRESHOLDS (AUTO MODE)
Speed X Threshold
: sets the value of the ICS (in terms of percentage) that,
being in the fan speed number X–1, will trigger speed number X while in the
automatic mode. In other words, the successive thresholds define different
ranges for the ICS, each one corresponding to a particular fan speed.