MAXinBOX FC 0-10V VALVE
http://www.zennio.com
Technical Support:
http://zennioenglish.zendesk.com
40
MINIMUM SPEED (MANUAL MODE)
Minimum Manual Speed With Open Valve in Cooling Mode
: sets a minimum
fan speed to ensure the fan never adopts lower speeds while the cooling valve
is open and the speed control remains manual. Note that speed 0 is not
permitted in any case while the valve is open.
Minimum Manual Speed With Open Valve in Heating Mode
: analogous to
the above parameter, but for the heating valve.
ADVANCED FAN CONFIGURATION
Delays
: enables the “Delays” function. See section 2.5.3.1.
Silent Mode
: enables the “Silent Mode” function. See section 2.5.3.2.
Note
:
this function can only be enabled if the automatic fan speed control is
available
.
Custom Start
: enables the “Custom Start” function. See section 2.5.3.3.
2.5.3.1
DELAYS
It is possible to parameterise a series of delays over the fan operation:
Mode Switch Delays
: these delays will apply to the fan start-up after a
heating/cooling mode switchover, which can be useful to improve the comfort
of the user (immediate ventilation after the mode switchover may be
undesired).
Note that the mode switchover (i.e., opening one valve while closing the other
valve) can itself be delayed (see section 2.5.2). In such case, the total time
the fan will wait before responding to fan speed control orders will be the
result of summing up both delays.
Stop Delays
: in case the fan coil module has not been configured to remain
always on, these delays will apply to the switch-off of the fan after the module
itself is turned off.
In both cases, it is possible to configure different delays for each mode (cooling /
heating).