MAXinBOX FC 0-10V VALVE
http://www.zennio.com
Technical Support:
http://zennioenglish.zendesk.com
48
Disabled output
: outputs disabled in parameters will not react to button
presses under the Test Off mode.
Regarding any other secondary functions, the device will behave under the Test Off
mode as usual. Button presses during this mode are entirely analogous to the
reception of the corresponding orders from the KNX bus.
Test On Mode
After entering the Test On mode, it will only be possible to control the outputs through
the on-board pushbuttons. Orders received through communication objects will be
ignored, with independence of the output they are addressed to.
Depending on the type of output, binary or analogue, the reactions to the button
presses will differ.
Binary output
: the behaviour is analogous as in the Test Off mode, although
the status objects will not change.
0-10V analogue output
: the behaviour is the same as described for the Test
Off Mode, although the status objects will not change.
Disabled output
: under the Test On mode, disabled outputs will behave as if
they were enabled, thus, as described above (depending on whether they are
binary or analogue outputs).
Any other secondary functions will not work while the device is under the Test On
mode, but will be taken into account when leaving the Test On mode. Status objects
will not be sent to the bus, either.
Important
:
the device is factory delivered with both manual modes (Test Off and Test
On) enabled
.