MAXinBOX FC 0-10V VALVE
http://www.zennio.com
Technical Support:
http://zennioenglish.zendesk.com
10
2.4
INDIVIDUAL 0-10V ANALOGUE OUTPUTS
MAXinBOX FC 0-10V VALVE incorporates
two analogue voltage outputs
that
provide a signal with a voltage in the range 0 to 10 VDC. This voltage will be in
accordance to the percentage values that are received through a specific
communication object.
These outputs can be enabled and configured independently in parameters
as long as
they are not required by the fan coil control module
(see section 2.5) as their
typical application in this device is controlling the opening and closing of the valves in
the fan coil pipes.
One on-board
LED indicator
is offered per output to show the status: it will remain off
while the output signal is 0V, and on while it is 10V. Under intermediate values, it will
blink with variable rates (according to the voltage).
ETS PARAMETERISATION
After enabling “
0-10V Analog Outputs
” in the General screen (see section 2.1), a new
tab will be incorporated into the tree on the left.
Figure 3
0-10V Analog Outputs - Configuration.
The two analogue outputs can be activated independently (provided that they are not in
use by the fan coil module; see section 2.5) by marking the checkboxes. This also
brings new tabs to the tree.
Figure 4
0-10V Analog Output X – Configuration.
After enabling any of them, two objects are included by default: