MAXinBOX FC 0-10V VALVE
http://www.zennio.com
Technical Support:
http://zennioenglish.zendesk.com
41
ETS PARAMETERISATION
Figure 17.
Fan Coil – Delays.
The Delays screen is accessible after enabling the Delays function (see section 2.5.3).
It contains the following parameters:
Fan Start Delay After Switching to Cooling Mode
: sets a delay (from 0 to
3600 seconds and from 0 to 1440 minutes) after commuting from heating to
cooling and before the fan can be switched on
.
Fan Star Delay After Switching to Heating Mode
: analogous to the above
parameter, but after switching from cooling to heating.
Fan Stop Delay After Off Order, Cooling Mode
: sets a delay (from 0 to
3600 seconds and from 0 to 1440 minutes) after turning off the fan coil
module in the cooling mode, and before the fan is switched off. In other
words, this sets an additional ventilation time after the fan coil module is
turned off while in the cooling mode.
Fan Stop Delay After Off Order, Heating Mode
: analogous to the above
parameter, but for the heating mode.